| 2015-06-23 16:25:52 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) SHEET CVR -PLEASE PROVIDE NOTE INDICATING COMPLIANCE |
| | WITH NFPA 150 STANDARD ON FIRE AND LIFE SAFETY IN |
| | ANIMAL HOUSING 2009 EDITION. |
| | |
| | 2) INDICATE, FOR EACH BUILDING, THE ANIMAL CATEGORY AND |
| | ANIMAL CLASS IN COMPLIANCE WITH NFPA 150. |
| | |
| | 3) INDICATE, FOR EACH BUILDING, IF A FIRE SPRINKLER |
| | AND/OR FIRE ALARM SYSTEM BE PROVIDED IN COMPLIANCE WITH |
| | NFPA 150 AND PROVIDE CONCEPTUAL DRAWINGS. SHOP DRAWINGS |
| | WILL BE REQUIRED SEPARATELY. |
| | |
| | 4) PROVIDE A DOOR SCHEDULE INCLUDING DOOR HARDWARE. |
| | |
| | 5) PROVIDE CAGE/GATE DETAIL FOR EACH KENNEL. |
| | |
| | 6) PROVIDE DETAIL ON ROLL DOWN GATES. DO THEY HAVE |
| | CLUTHCING SYSTEM TO PREVENT RAPID ROLL DOWN? WILL THEY |
| | BE ATTACHED TO FIRE ALARM SYSTEM? HOW WILL THEY BE |
| | ACCESSED IN EMERGENCY SITUATION? IS THERE A FAIL SAFE |
| | IN THE EVENT OF POWER FAILURE? |
| | |
| | 7) THE OVERNIGHT DOG SHELTER FLOOR LAYOUT INDICATES |
| | DEADEND CORRIDORS OVER 20'. PROVIDE FOR A SECOND EXIT |
| | OR PROVIDED ADDITIONAL DOORS TO CREATE A LOOP WITH |
| | PROPER EXIT SIGNAGE. |
| | |
| | 8) WILL THE CAMPUS BE STAFFED 24 HOURS? HOW WILL A FIRE |
| | ALARM/SPRINKLER ACTIVATION BE HANDLED? |
| | |
| | 9) HOW WILL EMERGENCY ACCESS TO THE CAMPUS BE PROVIDED. |
| | A KNOX BOX KEY SYSTEM IS RECOMMENDED. |
| | |
| | 10) THERE ARE EXIT DISCHARGES INTO AREAS THAT DO NOT |
| | APPEAR TO BE PUBLIC WAYS. EACH EACH SHALL LEAD TO A |
| | PUBLIC WAY. AREAS FENCED IN SHALL BE HAVE EXIT ACCESS |
| | GATES CLEARLY MARKED AS AN EXIT WITH PROPER EXIT |
| | HARDWARE ON THOSE GATES. |
| | |
| | 11) IF GAS APPLIANCES ARE INSTALLED A CARBON MONOXIDE |
| | DETECTION SYSTEM IS REQUIRED. |
| | |
| | 12) ADDITIONAL COMMENTS MAY BE PROVIDED WITH THE ABOVE |
| | RESUBMITTALS. |
| | |