Plan Review Notes
Plan Review Notes For Permit 15060795
Permit Number 15060795
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2015-06-23 16:25:52THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET CVR -PLEASE PROVIDE NOTE INDICATING COMPLIANCE
 WITH NFPA 150 STANDARD ON FIRE AND LIFE SAFETY IN
 ANIMAL HOUSING 2009 EDITION.
  
 2) INDICATE, FOR EACH BUILDING, THE ANIMAL CATEGORY AND
 ANIMAL CLASS IN COMPLIANCE WITH NFPA 150.
  
 3) INDICATE, FOR EACH BUILDING, IF A FIRE SPRINKLER
 AND/OR FIRE ALARM SYSTEM BE PROVIDED IN COMPLIANCE WITH
 NFPA 150 AND PROVIDE CONCEPTUAL DRAWINGS. SHOP DRAWINGS
 WILL BE REQUIRED SEPARATELY.
  
 4) PROVIDE A DOOR SCHEDULE INCLUDING DOOR HARDWARE.
  
 5) PROVIDE CAGE/GATE DETAIL FOR EACH KENNEL.
  
 6) PROVIDE DETAIL ON ROLL DOWN GATES. DO THEY HAVE
 CLUTHCING SYSTEM TO PREVENT RAPID ROLL DOWN? WILL THEY
 BE ATTACHED TO FIRE ALARM SYSTEM? HOW WILL THEY BE
 ACCESSED IN EMERGENCY SITUATION? IS THERE A FAIL SAFE
 IN THE EVENT OF POWER FAILURE?
  
 7) THE OVERNIGHT DOG SHELTER FLOOR LAYOUT INDICATES
 DEADEND CORRIDORS OVER 20'. PROVIDE FOR A SECOND EXIT
 OR PROVIDED ADDITIONAL DOORS TO CREATE A LOOP WITH
 PROPER EXIT SIGNAGE.
  
 8) WILL THE CAMPUS BE STAFFED 24 HOURS? HOW WILL A FIRE
 ALARM/SPRINKLER ACTIVATION BE HANDLED?
  
 9) HOW WILL EMERGENCY ACCESS TO THE CAMPUS BE PROVIDED.
 A KNOX BOX KEY SYSTEM IS RECOMMENDED.
  
 10) THERE ARE EXIT DISCHARGES INTO AREAS THAT DO NOT
 APPEAR TO BE PUBLIC WAYS. EACH EACH SHALL LEAD TO A
 PUBLIC WAY. AREAS FENCED IN SHALL BE HAVE EXIT ACCESS
 GATES CLEARLY MARKED AS AN EXIT WITH PROPER EXIT
 HARDWARE ON THOSE GATES.
  
 11) IF GAS APPLIANCES ARE INSTALLED A CARBON MONOXIDE
 DETECTION SYSTEM IS REQUIRED.
  
 12) ADDITIONAL COMMENTS MAY BE PROVIDED WITH THE ABOVE
 RESUBMITTALS.
  