Plan Review Notes
Plan Review Notes For Permit 15060795
Permit Number 15060795
Review Stop E
Sequence Number 1
Notes
Date Text
2015-08-07 10:22:421ST REVIEW: FBC 2010/NEC 2008
  
 REVIEW DENIED. INFORMATION PROVIDED IS INSUFFICIENT.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS..
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  
 PLEASE PROVIDE PER FBC- 107.3.5.3 ? ELECTRIC SERVICE
 RISER WITH WIRE SIZES, CONDUIT DETAIL AND GROUNDING
 DETAIL. COMPLETE LOAD CALCULATIONS, PANEL SCHEDULES AND
 SHOW CIRCUITS ON FLOOR PLAN. T
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  