| 2015-07-07 08:06:38 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT:15060795 |
| | ADD: 1016 CLEARWATER PL. |
| | CONT: SIDNEY SCHREIDELL |
| | TEL: (954)214-7908 |
| | E-MAIL: |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. JULY 07/2015 |
| | ACTION: DENIED |
| | |
| | 1) THE COVERSHEET: |
| | 1A) THE OCCUPANCY CLASSIFICATION IS LISTED AS AN A3- |
| | BUT THE PLANS INDICATE THE USAGE BEING A ANIMAL KENNEL, |
| | PLEASE REVIEW 2010 FBC-B SECTION 304.1 IT APPEARS THE |
| | OCCUPANCY SHOULD BE A BUSINESS OCCUPANCY. |
| | |
| | 1B) UNDER THE HEADING OF OCCUPANCY LOADS INDICATES AN |
| | ADDITION BUT THERE IS A NOTE FURTHER DOWN THE PAGE THAT |
| | THERE IS NO CHANGE OF SQUARE FOOTAGE. 2010 WEST PALM |
| | BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER |
| | 1, ADMINISTRATION, 107.2.1.3 ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 1C) PLEASE NOTE THE PLANS INDICATE AN ASSEMBLY |
| | OCCUPANCY OF 305 SQ. FT/ 11 = 28 OCCUPANTS ALWAYS ROUND |
| | UP TO THE NEXT WHOLE PERSONS, WE DON'T HAVE PARTS OF |
| | OCCUPANTS THEY ONLY COME IN A WHOLE PERSON. ALSO THE |
| | SQUARE FOOTAGE IS UNDER 750 SQ. FT WHICH WOULD TRIGGER |
| | THE ASSEMBLY OCCUPANCY WHEN THE OCCUPANT LOAD IS |
| | FIGURED AT 15 SQ. FT./ OCCUPANT, ALSO NOTE FOR A MIXED |
| | USE OCCUPANCY THE ACCESSORY OCCUPANCY HAS TO BE AT |
| | LEAST 10% OF THE BUILDING AREA FOR THAT STORY TO BECOME |
| | MIXED USE. |
| | |
| | 1D) IN THE DESCRIPTION OF WORK TO BE COMPLETED UNDER |
| | THIS PERMIT, WITH THE REMOVAL OF A CONCRETE DRIVEWAY |
| | AND ASPHALT PARKING LOT THIS WORK IS LOCATED ON AN |
| | ADJOINING LOT. THE AERIAL VIEW SHOWS WORK AT 1022 |
| | CLEARWATER PL. EITHER A SEPARATE PERMIT NEEDS TO BE |
| | APPLIED FOR OR A UNITY OF TITLE TO UNIFY THE (2) LOTS. |
| | |
| | 2) SHEET SP-3 SHOWS ACCESSIBLE PARKING DETAILS, THEY |
| | NEED TO BE TO THE CITY OF WEST PALM BEACH STANDARDS SEE |
| | MUNI CODE 94-485 STALL PAINTING DETAIL. |
| | 2010 FBC- ACCESSIBILITY 502.3.3. |
| | |
| | 3) SHEET A-3 EXISTING AND NEW DOORS ALL 3 BUILDINGS ARE |
| | EITHER SHOWN AS 2'-6" OR 2'-8" PLEASE PROVIDE |
| | COMPLIANCE WITH 2010 FBC-B SECTION 1008.1.1 SIZE OF |
| | DOORS A MINIMUM OF 32" CLEAR OPENING OF THE DOOR. THIS |
| | IS MEASURED WITH THE FACE OF THE DOOR TO THE OPPOSITE |
| | SIDE DOOR STOP. FOR 32 INCHES CLEAR A MINIMUM OF A |
| | 2'-10" IS REQUIRED. |
| | ALSO SEE 2010 FBC-ACCESSIBILITY CODE 404.2.3 CLEAR |
| | WIDTH. |
| | |
| | 3A) BUILDING # 2 THE DOOR TO THE LEFT SIDE OF THE FOYER |
| | THAT LEADS TO THE DOG KENNELS DOES NOT HAVE THE CLEAR |
| | FLOOR SPACE REQUIRED ON THE KENNEL SIDE OF THE DOOR SEE |
| | FL ACCESS. FIGURE 404.2.4.1(J) REQUIRES A MINIMUM OF 42 |
| | INCHES. |
| | |
| | 3B) PLEASE INDICATE WHERE THE GATES OR DOORS WILL BE ON |
| | THE FRONT OF THE KENNELS, IT APPEARS THERE WILL BE ALOT |
| | OF DOORS THAT WILL NOT HAVE THE REQUIRED 18" ON THE |
| | LATCH SIDE OF THE DOOR. 2010 FBC-ACCESSIBILITY CODE |
| | 404.2.4. |
| | |
| | 3C) BUILDING # 3 IN BOTH DOOG AREAS 246 SQ. FT & 270 |
| | SQ. FT. THE INSWING DOORS ARE MISSING THE REQUIRED 18 |
| | INCHES REQUIRED BY ACCESS. CODE 404.2.4. |
| | |
| | 3D) THE HALLWAY DOOR DIRECTLY IN FRONT OF THE OFFICE IS |
| | ALSO MISSING THE REQUIRED 18 INCHES REQUIRED BY THE |
| | 2010 FBC-ACCESS. CODE 404.2.4. |
| | |
| | 3E) THE NEW ACCESSIBLE RESTROOM IS NOT DEMINSIONED SO |
| | CODE COMPLIANCE WITH 2010 FBC-ACCESSIBILITY CODE |
| | SECTION 604.3.2 CAN NOT BE DETERMINED. |
| | |
| | 4) SHEET A4 THE LIFE SAFETY SHEET NOR THE COVER SHEET |
| | INDICATE IF THE BUILDING IS FIRE SPRINKLERED OR NOT. |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 107.3.5.1.1 MINIMUM |
| | PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | |
| | 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |