2015-07-07 08:06:38BUILDING PLAN REVIEW
 W. P. B. PERMIT:15060795
 ADD: 1016 CLEARWATER PL.
 CONT: SIDNEY SCHREIDELL
 TEL: (954)214-7908
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JULY 07/2015
 ACTION: DENIED
  
 1) THE COVERSHEET:
 1A) THE OCCUPANCY CLASSIFICATION IS LISTED AS AN A3-
 BUT THE PLANS INDICATE THE USAGE BEING A ANIMAL KENNEL,
 PLEASE REVIEW 2010 FBC-B SECTION 304.1 IT APPEARS THE
 OCCUPANCY SHOULD BE A BUSINESS OCCUPANCY.
  
 1B) UNDER THE HEADING OF OCCUPANCY LOADS INDICATES AN
 ADDITION BUT THERE IS A NOTE FURTHER DOWN THE PAGE THAT
 THERE IS NO CHANGE OF SQUARE FOOTAGE. 2010 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION, 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 1C) PLEASE NOTE THE PLANS INDICATE AN ASSEMBLY
 OCCUPANCY OF 305 SQ. FT/ 11 = 28 OCCUPANTS ALWAYS ROUND
 UP TO THE NEXT WHOLE PERSONS, WE DON'T HAVE PARTS OF
 OCCUPANTS THEY ONLY COME IN A WHOLE PERSON. ALSO THE
 SQUARE FOOTAGE IS UNDER 750 SQ. FT WHICH WOULD TRIGGER
 THE ASSEMBLY OCCUPANCY WHEN THE OCCUPANT LOAD IS
 FIGURED AT 15 SQ. FT./ OCCUPANT, ALSO NOTE FOR A MIXED
 USE OCCUPANCY THE ACCESSORY OCCUPANCY HAS TO BE AT
 LEAST 10% OF THE BUILDING AREA FOR THAT STORY TO BECOME
 MIXED USE.
  
 1D) IN THE DESCRIPTION OF WORK TO BE COMPLETED UNDER
 THIS PERMIT, WITH THE REMOVAL OF A CONCRETE DRIVEWAY
 AND ASPHALT PARKING LOT THIS WORK IS LOCATED ON AN
 ADJOINING LOT. THE AERIAL VIEW SHOWS WORK AT 1022
 CLEARWATER PL. EITHER A SEPARATE PERMIT NEEDS TO BE
 APPLIED FOR OR A UNITY OF TITLE TO UNIFY THE (2) LOTS.
  
 2) SHEET SP-3 SHOWS ACCESSIBLE PARKING DETAILS, THEY
 NEED TO BE TO THE CITY OF WEST PALM BEACH STANDARDS SEE
 MUNI CODE 94-485 STALL PAINTING DETAIL.
 2010 FBC- ACCESSIBILITY 502.3.3.
  
 3) SHEET A-3 EXISTING AND NEW DOORS ALL 3 BUILDINGS ARE
 EITHER SHOWN AS 2'-6" OR 2'-8" PLEASE PROVIDE
 COMPLIANCE WITH 2010 FBC-B SECTION 1008.1.1 SIZE OF
 DOORS A MINIMUM OF 32" CLEAR OPENING OF THE DOOR. THIS
 IS MEASURED WITH THE FACE OF THE DOOR TO THE OPPOSITE
 SIDE DOOR STOP. FOR 32 INCHES CLEAR A MINIMUM OF A
 2'-10" IS REQUIRED.
 ALSO SEE 2010 FBC-ACCESSIBILITY CODE 404.2.3 CLEAR
 WIDTH.
  
 3A) BUILDING # 2 THE DOOR TO THE LEFT SIDE OF THE FOYER
 THAT LEADS TO THE DOG KENNELS DOES NOT HAVE THE CLEAR
 FLOOR SPACE REQUIRED ON THE KENNEL SIDE OF THE DOOR SEE
 FL ACCESS. FIGURE 404.2.4.1(J) REQUIRES A MINIMUM OF 42
 INCHES.
  
 3B) PLEASE INDICATE WHERE THE GATES OR DOORS WILL BE ON
 THE FRONT OF THE KENNELS, IT APPEARS THERE WILL BE ALOT
 OF DOORS THAT WILL NOT HAVE THE REQUIRED 18" ON THE
 LATCH SIDE OF THE DOOR. 2010 FBC-ACCESSIBILITY CODE
 404.2.4.
  
 3C) BUILDING # 3 IN BOTH DOOG AREAS 246 SQ. FT & 270
 SQ. FT. THE INSWING DOORS ARE MISSING THE REQUIRED 18
 INCHES REQUIRED BY ACCESS. CODE 404.2.4.
  
 3D) THE HALLWAY DOOR DIRECTLY IN FRONT OF THE OFFICE IS
 ALSO MISSING THE REQUIRED 18 INCHES REQUIRED BY THE
 2010 FBC-ACCESS. CODE 404.2.4.
  
 3E) THE NEW ACCESSIBLE RESTROOM IS NOT DEMINSIONED SO
 CODE COMPLIANCE WITH 2010 FBC-ACCESSIBILITY CODE
 SECTION 604.3.2 CAN NOT BE DETERMINED.
  
 4) SHEET A4 THE LIFE SAFETY SHEET NOR THE COVER SHEET
 INDICATE IF THE BUILDING IS FIRE SPRINKLERED OR NOT.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107.3.5.1.1 MINIMUM
 PLAN REVIEW CRITERIA FOR BUILDINGS.
  
 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676