| Plan Review Notes For Permit 15060794 |
| Permit Number |
15060794 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-07-16 10:42:22 | ELECTRICAL PROVISO | | | PERMIT #15060794 | | | 1. GENERAL ELECTRICAL NOTES TO BE AMENDED TO INCLUDE, | | | ?SMOKE DETECTORS SHALL HAVE BATTERY BACK-UP AND BE | | | INTER-CONNECTED. | | | 2. ALL OUTLET BOXES IN A FIRE RATED WALL SHALL BE | | | PROTECTED WITH LISTED FIRE-BLOCKING MATERIAL. | | | 3. ALL CEILING LUMINAIRE OUTLETS SHALL BE RATED TO | | | SUPPORT 50LBS. PER NEC 314.27. | | | | | | |
|