Plan Review Notes
Plan Review Notes For Permit 15060794
Permit Number 15060794
Review Stop E
Sequence Number 1
Notes
Date Text
2015-07-16 10:42:22ELECTRICAL PROVISO
 PERMIT #15060794
 1. GENERAL ELECTRICAL NOTES TO BE AMENDED TO INCLUDE,
 ?SMOKE DETECTORS SHALL HAVE BATTERY BACK-UP AND BE
 INTER-CONNECTED.
 2. ALL OUTLET BOXES IN A FIRE RATED WALL SHALL BE
 PROTECTED WITH LISTED FIRE-BLOCKING MATERIAL.
 3. ALL CEILING LUMINAIRE OUTLETS SHALL BE RATED TO
 SUPPORT 50LBS. PER NEC 314.27.
  
  