2015-10-27 16:30:223RD REVIEW: FBC 2014 MECHANICAL
 PERMIT #15060791
 10/27/15
  
 1) PROVIDE EQUIPMENT SCHEDULES ON THE PLANS FOR THE
 INTAKE AND EXHAUST FANS INCLUDING MAKES AND MODELS, CFM
 CAPACITIES, ELECTRICAL DATA ETC.
 2) THE MECHANICAL DAMPERS SHOWN ON THE EXTRERIOR WALLS
 COVERING THE FANS MUST BE WIND AND WATER RESISTANT- SEE
 SECTIONS 401.5 AND 501.2.2 FBC-10 MECHANICAL AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS THAT INDICATE COMPLIANCE.
 3) PLEASE REFER TO SECTION 1609.1.2 (PROTECTION OF
 OPENINGS) AND 1609.6.4.4.1 (COMPONENTS AND CLADDING)
 FBC-10 BUILDING, AND PROVIDE TWO COPIES OF FLORIDA
 PRODUCT APPROVALS OR MIAMI-DADE NOA'S FOR THE DAMPERS-
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3.
 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 FLEXIBLE EXHAUST HOSES. REFER TO SECTION 501.4: EXHAUST
 DUCTS SHALL BE OF METAL AND SUCH CONSTRUCTION SHALL
 COMPLY WITH CHAPTER 6 FBC-10 MECHANICAL. PLEASE NOTE
 THAT THIS SECTION DOES NOT RESTRICT THE USE OF
 ALTERNATE MATERIALS IF LISTED AND LABELED FOR THE USE
 SPECIFIED ON THE PLAN.
 5) IT APPEARS THAT THE EXHAUST DISCHARGE AT THE REAR OF
 THE BUILDING IS WITHIN THE MINIMUM 10 FT. REQUIRED
 CLEARANCE DISTANCE TO THE REAR DOOR OPENING- REFER TO
 SECTION 501.2.1 FBC-10 MECHANICAL AND INDICATE
 COMPLIANCE.
 6) INDICATE THE CLEARANCE DISTANCE MEASUIREMENT FROM
 THE NEW AIR INTAKE AT THE REAR OF THE BUILDING TO THE
 PARKING LOT AND DRIVE AREAS- REFER TO SECTION 401.4 AND
 401.4.1 FBC-10 MECHANICAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER