| 2015-10-28 14:01:24 | THE FAILURE TO PROVIDE A NARRATIVE OF THE CORRECTIONS |
| | AS REQUIRED PROMPTED FOR A COMPLETE REVIEW OF THE |
| | PLANS. THIS REVIEW PROVED THAT THE PREVIOUS COMMENTS |
| | WERE NOT FULLY ADDRESSED. BELOW ARE THE RESULTS OF THE |
| | THIRD REVIEW |
| | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE 2008 EDITION |
| | OF THE NEC, (NATIONAL ELECTRICAL CODE); 2010 EDITION OF |
| | THE FBC, (FLORIDA BUILDING CODE) AS APPLICABLE AND |
| | BELOW ARE THE DEFICIENCIES NOTED. |
| | 1. FOR SAFE EMERGENCY EGRESS, AN EMERGENCY LIGHT SHALL |
| | BE INSTALLED IN THE ELECTRICAL ROOM. AN ADDITIONAL |
| | EMERGENCY LIGHT SHALL BE INSTALLED IN THE HAIR WASH |
| | AREA, AND ANY OTHER AREA AS REQUIRED BY CODE. |
| | 2. PER NFPA 101 SECTION 7.10.1.5.1 ALL EXITS SHALL BE |
| | MARKED WITH APPROVED READILY VISIBLE SIGNS. THE WAY |
| | TOWARDS THE EXITS, IF NOT READILY APPARENT SHALL BE |
| | MARKED AS WELL. |
| | 3. NEC 1101.26(D) REQUIRES THAT PROPER ILLUMINATION BE |
| | PROVIDED FOR ALL WORKING SPACES ABOUT ELECTRICAL |
| | PANELS. THE AREA IN FRONT OF ELECTRICAL PANEL ?A? IS |
| | LACKING SAFE WORKING ILLUMINATION. |
| | 4. FBC-ENERGY CONSERVATION SECTION 502.3.8 REQUIRES |
| | THAT ALL RECESSED LIGHTING INSTALLED IN THE BUILDING |
| | ENVELOPE SHALL BE IC PROTECTED AND AIR-TIGHT RATED & |
| | SEALED TO PREVENT AIR LEAKAGE BETWEEN THE CONDITIONED |
| | AND UNCONDITIONED SPACE. |
| | 5. NEC 422.52 REQUIRES THAT THE ELECTRIC WATER COOLER |
| | BE CONNECTED TO A GFCI PROTECTED CIRCUIT. |
| | 6. NEC 600.5 REQUIRES THAT EVERY COMMERCIAL OCCUPANCY |
| | BE PROVIDED WITH A DEDICATED 20 AMP CIRCUIT FOR SIGN OR |
| | OUTLINE LIGHTING AT EACH PEDESTRIAN ENTRANCE. |
| | 7. NEC 422.30(B) REQUIRES THAT THERE BE A DISCONNECT |
| | FOR THE 80 GAL STORAGE WATER HEATER. |
| | 8. THE 5TH ED. 2014 FBC-ENERGY CONSERVATION SECTION 505 |
| | HAS SPECIFIC REQUIREMENTS FOR COMMERCIAL LIGHTING WHICH |
| | SHALL BE ADHERED TO. IN ADDITION TO THE LIGHT DENSITY |
| | CHART, THERE ARE MANDATORY SWITCHING REQUIREMENTS WHICH |
| | SHALL BE PROVIDED. |
| | 9. YOU SHALL PROVIDE SITE SPECIFIC LOAD CALCS IN |
| | ACCORDANCE TO NEC 220 PART III. YOUR LOAD CALCS AS |
| | SUBMITTED DO NOT MATCH THE PANEL ESTIMATED LOADS. |
| | 10. INDICATE THE LOCATION OF THE HVAC EQUIPMENT ON THE |
| | ELECTRICAL FLOOR PLAN. YOU DO NOT HAVE ANY HVAC |
| | DRAWINGS OR SPECIFICATIONS ON THE PLANS. |
| | THE PLANS SHALL BE REVISED TO ADDRESS THE HEREIN |
| | MENTIONED ITEMS; ONCE CORRECTED SHALL BE RESUBMITTED |
| | FOR ANOTHER REVIEW. |
| | WHEN RESUBMITTING, YOU ARE REQUIRED TO PROVIDE A |
| | RESPONSE LETTER ADDRESSING EACH ITEM ACCOMPANIED WITH |
| | THE STANDARD CITY RE-SUBMITTAL FORM. |
| | PLEASE, ADDITIONALLY, INSERT CORRECTED PAGES INTO THE |
| | SUBMITTAL AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARISON. CLOUDING THE CHANGES WILL BE GREATLY |
| | APPRECIATED. |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | PURSUANT TO FS553.80, THE 4TH SUBMITTAL FOR A PERMIT |
| | WHICH REFLECTS FAILURE TO CORRECT A DEFICIENCY |
| | PREVIOUSLY SPECIFICALLY AND CONSISTENTLY IDENTIFIED ON |
| | ALL PRIOR SUBMITTALS MUST RESULT IN THE ASSESSMENT OF A |
| | PENALTY OF 3 TIMES THE PLAN REVIEW FEE IN ADDITION TO |
| | THE NORMAL FEE. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | |