Plan Review Notes
Plan Review Notes For Permit 15060791
Permit Number 15060791
Review Stop E
Sequence Number 3
Notes
Date Text
2015-10-28 14:01:24THE FAILURE TO PROVIDE A NARRATIVE OF THE CORRECTIONS
 AS REQUIRED PROMPTED FOR A COMPLETE REVIEW OF THE
 PLANS. THIS REVIEW PROVED THAT THE PREVIOUS COMMENTS
 WERE NOT FULLY ADDRESSED. BELOW ARE THE RESULTS OF THE
 THIRD REVIEW
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE 2008 EDITION
 OF THE NEC, (NATIONAL ELECTRICAL CODE); 2010 EDITION OF
 THE FBC, (FLORIDA BUILDING CODE) AS APPLICABLE AND
 BELOW ARE THE DEFICIENCIES NOTED.
 1. FOR SAFE EMERGENCY EGRESS, AN EMERGENCY LIGHT SHALL
 BE INSTALLED IN THE ELECTRICAL ROOM. AN ADDITIONAL
 EMERGENCY LIGHT SHALL BE INSTALLED IN THE HAIR WASH
 AREA, AND ANY OTHER AREA AS REQUIRED BY CODE.
 2. PER NFPA 101 SECTION 7.10.1.5.1 ALL EXITS SHALL BE
 MARKED WITH APPROVED READILY VISIBLE SIGNS. THE WAY
 TOWARDS THE EXITS, IF NOT READILY APPARENT SHALL BE
 MARKED AS WELL.
 3. NEC 1101.26(D) REQUIRES THAT PROPER ILLUMINATION BE
 PROVIDED FOR ALL WORKING SPACES ABOUT ELECTRICAL
 PANELS. THE AREA IN FRONT OF ELECTRICAL PANEL ?A? IS
 LACKING SAFE WORKING ILLUMINATION.
 4. FBC-ENERGY CONSERVATION SECTION 502.3.8 REQUIRES
 THAT ALL RECESSED LIGHTING INSTALLED IN THE BUILDING
 ENVELOPE SHALL BE IC PROTECTED AND AIR-TIGHT RATED &
 SEALED TO PREVENT AIR LEAKAGE BETWEEN THE CONDITIONED
 AND UNCONDITIONED SPACE.
 5. NEC 422.52 REQUIRES THAT THE ELECTRIC WATER COOLER
 BE CONNECTED TO A GFCI PROTECTED CIRCUIT.
 6. NEC 600.5 REQUIRES THAT EVERY COMMERCIAL OCCUPANCY
 BE PROVIDED WITH A DEDICATED 20 AMP CIRCUIT FOR SIGN OR
 OUTLINE LIGHTING AT EACH PEDESTRIAN ENTRANCE.
 7. NEC 422.30(B) REQUIRES THAT THERE BE A DISCONNECT
 FOR THE 80 GAL STORAGE WATER HEATER.
 8. THE 5TH ED. 2014 FBC-ENERGY CONSERVATION SECTION 505
 HAS SPECIFIC REQUIREMENTS FOR COMMERCIAL LIGHTING WHICH
 SHALL BE ADHERED TO. IN ADDITION TO THE LIGHT DENSITY
 CHART, THERE ARE MANDATORY SWITCHING REQUIREMENTS WHICH
 SHALL BE PROVIDED.
 9. YOU SHALL PROVIDE SITE SPECIFIC LOAD CALCS IN
 ACCORDANCE TO NEC 220 PART III. YOUR LOAD CALCS AS
 SUBMITTED DO NOT MATCH THE PANEL ESTIMATED LOADS.
 10. INDICATE THE LOCATION OF THE HVAC EQUIPMENT ON THE
 ELECTRICAL FLOOR PLAN. YOU DO NOT HAVE ANY HVAC
 DRAWINGS OR SPECIFICATIONS ON THE PLANS.
 THE PLANS SHALL BE REVISED TO ADDRESS THE HEREIN
 MENTIONED ITEMS; ONCE CORRECTED SHALL BE RESUBMITTED
 FOR ANOTHER REVIEW.
 WHEN RESUBMITTING, YOU ARE REQUIRED TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ACCOMPANIED WITH
 THE STANDARD CITY RE-SUBMITTAL FORM.
 PLEASE, ADDITIONALLY, INSERT CORRECTED PAGES INTO THE
 SUBMITTAL AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARISON. CLOUDING THE CHANGES WILL BE GREATLY
 APPRECIATED.
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 PURSUANT TO FS553.80, THE 4TH SUBMITTAL FOR A PERMIT
 WHICH REFLECTS FAILURE TO CORRECT A DEFICIENCY
 PREVIOUSLY SPECIFICALLY AND CONSISTENTLY IDENTIFIED ON
 ALL PRIOR SUBMITTALS MUST RESULT IN THE ASSESSMENT OF A
 PENALTY OF 3 TIMES THE PLAN REVIEW FEE IN ADDITION TO
 THE NORMAL FEE.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
  