| 2015-09-10 14:12:22 | 1ST REVIEW: FBC 2014 | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | 561-805-6711 | | | [email protected] | | | | | | | | | | | | PLUMBING COMMENTS: | | | . | | | 1.WATER FOUNTAIN S SHALL COMPLY WITH FBC ACC. SEC. | | | 211.2 MINIMUM NUMBER. | | | NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. | | | ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH | | | 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.7 | | | 2. PROVIDE INFORMATION AND MANUFACTURE SPEC SHEETS ON | | | THE PEDICURE CHAIRS. DELETING THEM OFF PLUMBING PLAN | | | DOES NOT COMPLY WE NEED TO SEE HOW THEY WORK . | | | WPB AMEND. 107.2.1 |
|