| 2015-09-09 08:29:55 | 2ND REVIEW: FBC 2010 MECHANICAL |
| | PERMIT #15060791 |
| | 9/9/2015 |
| | |
| | 1) COMMENT #1 FROM THE 1ST REVIEW STILL EXISTS. |
| | ALTHOUGH THE REVISED PLAN DOES SHOW A NEW EXHAUST FAN, |
| | THE LOCATION OF THE FAN DOES NOT COMPLY WITH FOOTNOTE H |
| | UNDER TABLE 403.3 FBC-10 MECHANICAL WHICH REQUIRES |
| | CONTAMINANTS AND ODORS TO BE CAPTURED AT THEIR SOURCES. |
| | I AM RE-PRINTING THE COMMENT HERE FOR REVIEW: |
| | (AN EXHAUST VENTILATION SYSTEM DESIGNED IN ACCORDANCE |
| | WITH TABLE 403.3 FBC-20 MECHANICAL IS REQUIRED FOR THE |
| | NEW NAIL SALON. PLEASE REFER TO FOOTNOTES B AND H AT |
| | THE BOTTOM OF THE TABLE FOR SPECIFIC REQUIREMENTS FOR |
| | NAIL SALONS: B) MECHANICAL EXHAUST IS REQUIRED AND THE |
| | RECIRCULATION OF AIR FROM SUCH SPACES IS PROHIBITED |
| | (SEE SECTION 403.2.1, ITEM 3: WHERE MECHANICAL EXHAUST |
| | IS REQUIRED BY NOTE B IN TABLE 403.3, RECIRCULATION OF |
| | AIR FROM SUCH SPACES SHALL BE PROHIBITED. ALL AIR |
| | SUPPLIED TO SUCH SPACES SHALL BE EXHAUSTED, INCLUDING |
| | ANY AIR IN EXCESS OF THAT REQUIRED BY TABLE 403.3). H) |
| | FOR NAIL SALONS, THE REQUIRED EXHAUST SHALL INCLUDE |
| | VENTILATION TABLES OR OTHER SYSTEMS THAT CAPTURE THE |
| | CONTAMINANTS AND ODORS AT THEIR SOURCE AND ARE CAPABLE |
| | OF EXHAUSTING A MINIMUM OF 50 CFM PER STATION. THIS |
| | REQUIREMENT APPLIES TO BOTH MANICURE AND PEDICURE |
| | STATIONS. PLEASE REVISE THE PLANS ACCORDINGLY.) IN |
| | ORDER FOR THE SALON TO BE IN COMPLIANCE, EXHAUST INLETS |
| | MUST BE PLACED AT EVERY MANICURE TABLE AND PEDICURE |
| | STATION IN THE FACILITY, AND MAKE-UP AIR MUST BE |
| | PROVIDED AT THESE LOCATIONS FOR THE EXHAUST. THE SYSTEM |
| | MUST BE INDEPENDENT OF THE MAIN HVAC SYSTEM, AND MUST |
| | BE DESIGNED TO BE AIR IN/ AIR OUT WITH NO RECIRCULATION |
| | OF EXHAUST. |
| | 2) PLEASE REVISE THE OUTDOOR AIR CALCULATIONS ON SHEET |
| | A-2 TO INCLUDE THE EXHAUST CFM'S PER SQ. FT., AND |
| | PROVIDE AN AIR BALANCE CALCULATION. |
| | |
| | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |
| | |