2015-09-16 19:03:05PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
 1. FOR SAFE EMERGENCY EGRESS, AN EMERGENCY LIGHT SHALL
 BE INSTALLED IN THE ELECTRICAL ROOM. AN ADDITIONAL
 EMERGENCY LIGHT SHALL BE INSTALLED IN THE HAIR WASH
 AREA.
 2. NEC 422.52, REQUIRES THAT THE ELECTRIC WATER COOLER
 BE CONNECTED TO A GFCI PROTECTED CIRCUIT.
 3. NEC 600.5, REQUIRES THAT EVERY COMMERCIAL OCCUPANCY
 BE PROVIDED WITH AT LEAST ONE OUTLET IN AN ACCESSIBLE
 LOCATION AT EACH ENTRANCE A DEDICATED 20 AMP CIRCUIT
 FOR SIGN OR OUTLINE LIGHTING
 4. NEC 422.30(B), REQUIRES THAT THERE BE A DISCONNECT
 FOR THE 80 GAL STORAGE WATER HEATER.
 5. NEC 210.70 (A)(2), REQUIRES THAT THE STAIRWAY BE
 ILLUMINATED AND THE LIGHT BE CONTROLLED BY A WALL
 SWITCH.
 6. THE 5TH ED. 2014 FBC-ENERGY CONSERVATION SECTION 505
 HAS SPECIFIC REQUIREMENTS FOR COMMERCIAL LIGHTING WHICH
 SHALL BE ADHERED TO.
 7. IN VARIOUS PLACES THROUGHOUT THE NOTES DIFFERENT
 NON-BINDING EDITIONS OF THE NEC ARE QUOTED. PLEASE
 CORRECT THE NOTES TO ADDRESS THE 2011 EDITION OF THE
 NEC.
 8. FIRE ALARM WORK, EVEN THOUGH SHALL BE UNDER A
 SEPARATE PERMIT AND SHOP DRAWING, SHALL BE DESIGNED TO
 COMPLY WITH NFPA 72, 2010 EDITION NOT THE NFPA 96.
 9. YOU SHALL INDICATE ON THE ELECTRICAL RISER DIAGRAM
 WHAT PORTIONS OF IT PERTAIN TO THIS SPECIFIC PROJECT,
 AND INDICATED THE CONDUCTOR SIZING FOR THE APPLICABLE
 PANELS.
 10. THE PANEL SCHEDULES AS PRESENTED DO NOT MATCH THE
 FLOOR PLAN MARKINGS AND CIRCUIT DESIGNATIONS.
 11. ACCORDING TO THE MARKINGS ON THE PANEL DESIGNATOR
 THIS IS A 3 PHASE SERVICE CONTRARY TO THE LAYOUT OF THE
 PANELS. CORRECT ACCORDINGLY.
 12. ACCORDING TO THE SAME PANEL DESIGNATOR, ALL PANELS
 ARE BOTTOM FED. IF THE FEEDERS ARE COMING FROM
 UNDERGROUND, CONDUCTOR INSULATION SHALL BE RATED FOR
 WET LOCATIONS AS INDICATED IN NEC 300.5 (B) AND THE
 ENDS OF THE RACEWAY SEALED ACCORDING TO NEC 300.5(G).
 13. YOU SHALL PROVIDE SITE SPECIFIC LOAD CALCS IN
 ACCORDANCE TO NEC 220 PART III.
 14. INDICATE THE LOCATION OF THE HVAC EQUIPMENT. YOU DO
 NOT HAVE ANY HVAC DRAWINGS OR SPECIFICATIONS ON THE
 PLANS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  