| 2015-09-16 19:03:05 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE |
| | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO |
| | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE |
| | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. |
| | 1. FOR SAFE EMERGENCY EGRESS, AN EMERGENCY LIGHT SHALL |
| | BE INSTALLED IN THE ELECTRICAL ROOM. AN ADDITIONAL |
| | EMERGENCY LIGHT SHALL BE INSTALLED IN THE HAIR WASH |
| | AREA. |
| | 2. NEC 422.52, REQUIRES THAT THE ELECTRIC WATER COOLER |
| | BE CONNECTED TO A GFCI PROTECTED CIRCUIT. |
| | 3. NEC 600.5, REQUIRES THAT EVERY COMMERCIAL OCCUPANCY |
| | BE PROVIDED WITH AT LEAST ONE OUTLET IN AN ACCESSIBLE |
| | LOCATION AT EACH ENTRANCE A DEDICATED 20 AMP CIRCUIT |
| | FOR SIGN OR OUTLINE LIGHTING |
| | 4. NEC 422.30(B), REQUIRES THAT THERE BE A DISCONNECT |
| | FOR THE 80 GAL STORAGE WATER HEATER. |
| | 5. NEC 210.70 (A)(2), REQUIRES THAT THE STAIRWAY BE |
| | ILLUMINATED AND THE LIGHT BE CONTROLLED BY A WALL |
| | SWITCH. |
| | 6. THE 5TH ED. 2014 FBC-ENERGY CONSERVATION SECTION 505 |
| | HAS SPECIFIC REQUIREMENTS FOR COMMERCIAL LIGHTING WHICH |
| | SHALL BE ADHERED TO. |
| | 7. IN VARIOUS PLACES THROUGHOUT THE NOTES DIFFERENT |
| | NON-BINDING EDITIONS OF THE NEC ARE QUOTED. PLEASE |
| | CORRECT THE NOTES TO ADDRESS THE 2011 EDITION OF THE |
| | NEC. |
| | 8. FIRE ALARM WORK, EVEN THOUGH SHALL BE UNDER A |
| | SEPARATE PERMIT AND SHOP DRAWING, SHALL BE DESIGNED TO |
| | COMPLY WITH NFPA 72, 2010 EDITION NOT THE NFPA 96. |
| | 9. YOU SHALL INDICATE ON THE ELECTRICAL RISER DIAGRAM |
| | WHAT PORTIONS OF IT PERTAIN TO THIS SPECIFIC PROJECT, |
| | AND INDICATED THE CONDUCTOR SIZING FOR THE APPLICABLE |
| | PANELS. |
| | 10. THE PANEL SCHEDULES AS PRESENTED DO NOT MATCH THE |
| | FLOOR PLAN MARKINGS AND CIRCUIT DESIGNATIONS. |
| | 11. ACCORDING TO THE MARKINGS ON THE PANEL DESIGNATOR |
| | THIS IS A 3 PHASE SERVICE CONTRARY TO THE LAYOUT OF THE |
| | PANELS. CORRECT ACCORDINGLY. |
| | 12. ACCORDING TO THE SAME PANEL DESIGNATOR, ALL PANELS |
| | ARE BOTTOM FED. IF THE FEEDERS ARE COMING FROM |
| | UNDERGROUND, CONDUCTOR INSULATION SHALL BE RATED FOR |
| | WET LOCATIONS AS INDICATED IN NEC 300.5 (B) AND THE |
| | ENDS OF THE RACEWAY SEALED ACCORDING TO NEC 300.5(G). |
| | 13. YOU SHALL PROVIDE SITE SPECIFIC LOAD CALCS IN |
| | ACCORDANCE TO NEC 220 PART III. |
| | 14. INDICATE THE LOCATION OF THE HVAC EQUIPMENT. YOU DO |
| | NOT HAVE ANY HVAC DRAWINGS OR SPECIFICATIONS ON THE |
| | PLANS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU |
| | |