Plan Review Notes
Plan Review Notes For Permit 15060791
Permit Number 15060791
Review Stop B
Sequence Number 2
Notes
Date Text
2015-09-21 14:38:47BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15060791
 ADD: 333 CLEMATIS ST.
 CONTRACTOR: HORMAK CONSTRUCTION
 TEL: (561)790-6863
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. SEPT. 21/2015
 ACTION: DENIED
  
 1A) COMPLIED. WILL NEED TO GET A CBC OR CGC ONBOARD FOR
 WORK BEYOND THE SCOPE OF YOUR LICENSE. FL S.S. 489.113.
  
 1B)VALUE IS STILL LOW AT $20,000.00. THE SUMMITED
 CONTRACT VALUE IS $23,500.00 AND THERE IS NO LINE ITEM
 FOR THE NEW STOREFRONT DOOR AND WALL SYSTEM.
 1ST REVIEW COMMENT. FOR THE WHOLE PROJECT THE VALUE OF
 $3,000.00 IS CONSIDERABLY LOW. 108.3* BUILDING PERMIT
 VALUATION.
  
 2) COMPLIED. SHEET A-1. THE RESTROOM DOORWAY NEXT TO
 THE REAR EXIT BLOCKS THE REAR EXIT, WILL NEED TO SWING
 INTO THE RESTROOM, SHOW COMPLIANCE WITH SECTION 2010
 FBC-B 1008.1.9.11 DURING ITS SWING, ANY DOOR IN A MEANS
 OF EGRESS SHALL LEAVE UNOBSTRUCTED AT LEAST ONE HALF OF
 THE REQUIRED WIDTH OF AN CORRIDOR, PASSAGEWAY OR
 LANDING, NOR PROJECT MORE THAN 7 INCHES INTO THE
 REQUIRED WIDTH OF CORRIDOR OR PASSAGEWAY.
  
 3) SEMI- COMPLIED. SHEET A-2 INDICATES THE WIND DESIGN
 CRITERIA. NOTE THE DESIGNER OF RECORD HAS INDICATED
 THAT THE EXPOSURE FOR THIS LOCATION IS A EXPOSURE D.
 THIS IS MORE RESTRICTIVE BUT IF THE DESIGNER OF ECORD
 WISHES TO DESIGN TO THE MORE RESTRICTIVE D EXPOSURE
 THEN THE PRESSURES ALSO WILL NEED TO MEET THE
 PRESSURES.
  
 THE PRESSURES FOR ROOF ZONES 1, 2 & 3 ALL INDICATE A
 PRESSURE OF 23.99 FOR 20 SQ. FT. THE FASTENING FOR
 ROOFS IS TAKEN AT 10 SQ. FT. FOR FASTENERS. THE DESIGN
 LIST THE VULT WIND SPEED OF 170 MPH. THE PRESSURES DO
 NOT INDICATE IF THEY ARE VULT OR VASD? THE ROOF
 PRESSURES IN VASD FOR A EXPOSURE D ARE FOR ZONE 1 ARE
 -50.4, ZONE 2 -108.4 & FOR ZONE 3 -127.3 @ 25 FT. MEAN
 ROOF HEIGHT.
  
 THE WINDOW PRESSURES WILL ALSO NEED TO INDICATE IF THEY
 ARE VULT OR VASD.
  
 COMMENT FROM THE 1ST REVIEW
 SHEET A-1 SHOWS A NEW GLASS STOREFRONT WINDOWS AND SET
 OF DOUBLE DOORS. PLEASE PROVIDE THE WIND DESIGN
 CRITERIA.
 . WIND DESIGN CRITERIA
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
  
  
 3.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 3.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 3.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 3.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 3.5) COMPONENTS & CLADDING PRESSURES POSITIVE &
 NEGATIVE TABLE 1609.2(2).
  
 4) 2ND REQUEST, UNTIL PRESSURES ARE INDICATED IN EITHER
 VULT OR VASD THE PRODUCT APPROVALS CAN NOT BE REVIEWED.
 COMPONENTS & CLADDING/ 2010 FBC-B 1609.1.2 PROTECTION
 OF OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) STOREFRONTS, CURTAIN WALLS, WALL LOUVERS, EFIS
 SYSTEMS
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (G) PRE-ENGINEERED A/C STANDS
  
 5) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 6) 2ND REQUEST. PLEASE PROVIDE ENERGY CALCULATIONS FOR
 THE NEW ADDITION. PROVIDE COMPLIANCE FOR THE SHGC OF
 THE GLAZING COMPLY WITH FBC-ENERGY TABLE 502.1.1.1(1)
 OR TABLE 502.1.1.1(2).
  
 7) 2ND REQUEST. DEALS WITH THE ELEVATED PEDICURE
 STATIONS AND THE RAISED PLATFORM BY TENANT. EITHER THE
 RAISED PLATFORM IS PART OF THE PERMIT AND THE WORK
 SHOWN OR IT IS NOT AND THE PEDICURE STATIONS ARE NOT
 SHOWN SINCE THEY WOULD NO LONGER BE IN THE SCOPE OF
 WORK.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION.
  
 AS FAR AS THE ACCESSIBLE PEDICURE STATION WITH A
 PORTABLE WASH TUB FOR SERVICE, IT WILL NEED TO SHOW A
 EQUIVALENCY TOO, 2010 FBC-ACCESSIBILITY CODE 103
 EQUIVALENT FACILITATION.
  
  
 COMMENT FROM THE 1ST REVIEW. SHEET A-1 SHOWS ELEVATED
 PEDICURE STATIONS AND A DETAIL 1 OF SHEET A-2. PLEASE
 SHOW COMPLIANCE WITH FBC-ACCESSIBILITY, VERTICAL
 ACCESSIBILITY TO PEDICURE STATIONS. 201.1.1.
  
 8) 2ND REQUEST, ADDITIONAL SQUARE FOOTAGE ADDED. BEFORE
 A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT FEES MUST
 BE PAID TO PALM BEACH COUNTY. THE ACTUAL PERMIT SET OF
 PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY OF THE
 PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE
 CALL (561)233-5025 FOR MORE INFORMATION.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  