Plan Review Notes
Plan Review Notes For Permit 15060791
Permit Number 15060791
Review Stop P
Sequence Number 1
Notes
Date Text
2015-06-20 06:39:011) SHT. A-1 - IDENTIFY THE ROOM WITH THE SINK THAT IS
 LOCATED NEAR THE HAIR WASH SINKS. WPB AMEND.TO 2010 FBC
 SEC. 107.2.1.
 2) A DRINKING FOUNTAIN IS REQUIRED IN A BUSINESS
 OCCUPANCY PER TABLE 403.1 OF THE 2010 FPC. NO FEWER
 THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED IN
 ACCORDANCE WITH THE 2010 FL. ACCESSIBILITY CODE SEC.
 211.2 & FOOTNOTE # E OF TABLE 403.1 OF FPC.
 3) ONE HAIR WASH SINK SHALL BE ACCESSIBLE PER SEC.212
 OF FL. ACCESSIBILITY CODE.
 4) SHT. A-3 - WATER HEATER DETAIL - THE RELIEF LINE
 SHALL DISCHARGE THROUGH AN AIR GAP LOCATED IN THE SAME
 ROOM AS THE WATER HEATER PERR 2010 FPC SEC. 504.6
 (2).THE PLAN SHOWS IT DISCHARGING TO THE EXTERIOR.
 5) IDENTIFY THE ACCESSIBLE RESTROOM ON THE FLOOR PLAN
 AND CLEARLY SHOW THE DIMENSIONS. (L X W). *5 INCHES IS
 THE MINIMUM WIDTH IF BUILT PERFECT, 86 INCHES ALLOWS
 FOR TOLERANCES.
 6) GRAB BARS SHALL BE MEASURED FORM THE FINISH FLOOR TO
 THE TOP OF THE GRIPPING SURFACE PER THE 2010 FAC SEC.
 609.4.
 7) SHT. P-2 - THE PEDICURE CHAIRS ARE NOT VENTED. 201
 FPC SEC.901.2.1.
 8) IF THE PEDICURE CHAIRS ARE GOING TO BE WET VENTED
 THE MAXIMUM NUMBER OF FIXTURE UNITS ON A HORIZONTAL WET
 VENT SHALL COMPLY WITH TABLE 909.3 OF 2010 FPC.
 9) SIZE THE LOOP VENT FOR THE HAIR SINKS. COMPLY WITH
 2010 FPC SEC. 916.1 & TABLE 916.1.
 10) CLEANOUTS ARE REQUIRED IN STACKS PER 2010 FPC
 SEC.708.3.4.
 11) SIZE ALL SECTIONS OF THE BUILDING DRAIN PER TABLE
 710.1 (1).
 12) SHT. P-2 CALLS OUT THE ADA BATH AS NEW & SHT. P-1
 NOTES IT AS EXISTING. CLARIFY.
 13) SHOW THE REQUIRED SHUTOFF VALVES TO THE PLUMBING
 FIXTURES PER 2010 FPC SEC.606.1, 606.2.
 14) SHT. P-2 - SHOW THE LOCATION WHERE THE WATER SUPPLY
 ENTERS THE STRUCTURE. WPB AMEND. TO 2010 FPC
 107.3.5.1.3.
 15) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS SHEETS AND INSRTALLATION MANUAL FOR THE
 PEDICURE CHAIRS.
 WPB AMEND.TO 2010 FBC SEC. 107.2.1.
 16) THE PLANS NOTE THAT THE APPLICABLE CODES ARE THE
 2014 FBC. THE CODE IN EFFECT FOR THIS PERMIT IS THE
 2010 FBC. CLARIFY.
 17) SHT. A-1 - NOTES THAT THE OCCUPANCY IS BASED ON AN
 AREA NOTED AS SALES AREA. THE TYPE OF OCCUPANCY FOR A
 NAIL SALON WOULD BE A BUSINESS OCCUPANCY. THE OCCUPANT
 LOAD WOULD BE 100 SQ. FT. PER PERSON BUT THE PLAN NOTES
 60 SQ. FT. PER PERSON. CLARIFY.
  