| 2015-06-20 06:39:01 | 1) SHT. A-1 - IDENTIFY THE ROOM WITH THE SINK THAT IS |
| | LOCATED NEAR THE HAIR WASH SINKS. WPB AMEND.TO 2010 FBC |
| | SEC. 107.2.1. |
| | 2) A DRINKING FOUNTAIN IS REQUIRED IN A BUSINESS |
| | OCCUPANCY PER TABLE 403.1 OF THE 2010 FPC. NO FEWER |
| | THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED IN |
| | ACCORDANCE WITH THE 2010 FL. ACCESSIBILITY CODE SEC. |
| | 211.2 & FOOTNOTE # E OF TABLE 403.1 OF FPC. |
| | 3) ONE HAIR WASH SINK SHALL BE ACCESSIBLE PER SEC.212 |
| | OF FL. ACCESSIBILITY CODE. |
| | 4) SHT. A-3 - WATER HEATER DETAIL - THE RELIEF LINE |
| | SHALL DISCHARGE THROUGH AN AIR GAP LOCATED IN THE SAME |
| | ROOM AS THE WATER HEATER PERR 2010 FPC SEC. 504.6 |
| | (2).THE PLAN SHOWS IT DISCHARGING TO THE EXTERIOR. |
| | 5) IDENTIFY THE ACCESSIBLE RESTROOM ON THE FLOOR PLAN |
| | AND CLEARLY SHOW THE DIMENSIONS. (L X W). *5 INCHES IS |
| | THE MINIMUM WIDTH IF BUILT PERFECT, 86 INCHES ALLOWS |
| | FOR TOLERANCES. |
| | 6) GRAB BARS SHALL BE MEASURED FORM THE FINISH FLOOR TO |
| | THE TOP OF THE GRIPPING SURFACE PER THE 2010 FAC SEC. |
| | 609.4. |
| | 7) SHT. P-2 - THE PEDICURE CHAIRS ARE NOT VENTED. 201 |
| | FPC SEC.901.2.1. |
| | 8) IF THE PEDICURE CHAIRS ARE GOING TO BE WET VENTED |
| | THE MAXIMUM NUMBER OF FIXTURE UNITS ON A HORIZONTAL WET |
| | VENT SHALL COMPLY WITH TABLE 909.3 OF 2010 FPC. |
| | 9) SIZE THE LOOP VENT FOR THE HAIR SINKS. COMPLY WITH |
| | 2010 FPC SEC. 916.1 & TABLE 916.1. |
| | 10) CLEANOUTS ARE REQUIRED IN STACKS PER 2010 FPC |
| | SEC.708.3.4. |
| | 11) SIZE ALL SECTIONS OF THE BUILDING DRAIN PER TABLE |
| | 710.1 (1). |
| | 12) SHT. P-2 CALLS OUT THE ADA BATH AS NEW & SHT. P-1 |
| | NOTES IT AS EXISTING. CLARIFY. |
| | 13) SHOW THE REQUIRED SHUTOFF VALVES TO THE PLUMBING |
| | FIXTURES PER 2010 FPC SEC.606.1, 606.2. |
| | 14) SHT. P-2 - SHOW THE LOCATION WHERE THE WATER SUPPLY |
| | ENTERS THE STRUCTURE. WPB AMEND. TO 2010 FPC |
| | 107.3.5.1.3. |
| | 15) SUBMIT TWO COPIES OF THE MANUFACTURER'S |
| | SPECIFICATIONS SHEETS AND INSRTALLATION MANUAL FOR THE |
| | PEDICURE CHAIRS. |
| | WPB AMEND.TO 2010 FBC SEC. 107.2.1. |
| | 16) THE PLANS NOTE THAT THE APPLICABLE CODES ARE THE |
| | 2014 FBC. THE CODE IN EFFECT FOR THIS PERMIT IS THE |
| | 2010 FBC. CLARIFY. |
| | 17) SHT. A-1 - NOTES THAT THE OCCUPANCY IS BASED ON AN |
| | AREA NOTED AS SALES AREA. THE TYPE OF OCCUPANCY FOR A |
| | NAIL SALON WOULD BE A BUSINESS OCCUPANCY. THE OCCUPANT |
| | LOAD WOULD BE 100 SQ. FT. PER PERSON BUT THE PLAN NOTES |
| | 60 SQ. FT. PER PERSON. CLARIFY. |
| | |