| Date |
Text |
| 2015-07-09 16:35:16 | 1ST REVIEW: FBC 2010 MECHANICAL |
| | PERMIT #15060791 7/9/15 |
| | |
| | 1) AN EXHAUST VENTILATION SYSTEM DESIGNED IN ACCORDANCE |
| | WITH TABLE 403.3 FBC-20 MECHANICAL IS REQUIRED FOR THE |
| | NEW NAIL SALON. PLEASE REFER TO FOOTNOTES B AND H AT |
| | THE BOTTOM OF THE TABLE FOR SPECIFIC REQUIREMENTS FOR |
| | NAIL SALONS: B) MECHANICAL EXHAUST IS REQUIRED AND THE |
| | RECIRCULATION OF AIR FROM SUCH SPACES IS PROHIBITED |
| | (SEE SECTION 403.2.1, ITEM 3: WHERE MECHANICAL EXHAUST |
| | IS REQUIRED BY NOTE B IN TABLE 403.3, RECIRCULATION OF |
| | AIR FROM SUCH SPACES SHALL BE PROHIBITED. ALL AIR |
| | SUPPLIED TO SUCH SPACES SHALL BE EXHAUSTED, INCLUDING |
| | ANY AIR IN EXCESS OF THAT REQUIRED BY TABLE 403.3). H) |
| | FOR NAIL SALONS, THE REQUIRED EXHAUST SHALL INCLUDE |
| | VENTILATION TABLES OR OTHER SYSTEMS THAT CAPTURE THE |
| | CONTAMINANTS AND ODORS AT THEIR SOURCE AND ARE CAPABLE |
| | OF EXHAUSTING A MINIMUM OF 50 CFM PER STATION. THIS |
| | REQUIREMENT APPLIES TO BOTH MANICURE AND PEDICURE |
| | STATIONS. PLEASE REVISE THE PLANS ACCORDINGLY. |
| | 2) THE SUBMITTED PLAN SHOWS A NEW O/A INTAKE PROVIDING |
| | 680 CFM TO THE AHU. PROVIDE A VENTILATION CALCULATION |
| | IN ACCORDANCE WITH TABLE 403.3 TO VERIFY THE MINIMUM |
| | RATE COMPLIANCE. |
| | 3) INDICATE ON THE PLAN THE AIR INTAKE OPENING WILL BE |
| | LOCATED TO MEET OR EXCEED THE REQUIRED CLEARANCE |
| | DISTANCES OUTLINED IN SECTION 401.4.1, AND THE OPENING |
| | WILL BE PROTECTED IN COMPLIANCE WITH 401.5. PROVIDE TWO |
| | COPIES OF A FLORIDA PRODUCT APPROVAL OR MIAMI-DADE NOA |
| | FOR THE INTAKE LOUVER. |
| | 4) A COMPLETE REVIEW OF THE PROJECT CANNOT BE COMPLETED |
| | AT THIS TIME DUE TO THE LACK OF DETAILS ON THE |
| | SUBMITTED PLANS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |
| | [email protected] |
| | |