Plan Review Notes
Plan Review Notes For Permit 15060791
Permit Number 15060791
Review Stop M
Sequence Number 1
Notes
Date Text
2015-07-09 16:35:161ST REVIEW: FBC 2010 MECHANICAL
 PERMIT #15060791 7/9/15
  
 1) AN EXHAUST VENTILATION SYSTEM DESIGNED IN ACCORDANCE
 WITH TABLE 403.3 FBC-20 MECHANICAL IS REQUIRED FOR THE
 NEW NAIL SALON. PLEASE REFER TO FOOTNOTES B AND H AT
 THE BOTTOM OF THE TABLE FOR SPECIFIC REQUIREMENTS FOR
 NAIL SALONS: B) MECHANICAL EXHAUST IS REQUIRED AND THE
 RECIRCULATION OF AIR FROM SUCH SPACES IS PROHIBITED
 (SEE SECTION 403.2.1, ITEM 3: WHERE MECHANICAL EXHAUST
 IS REQUIRED BY NOTE B IN TABLE 403.3, RECIRCULATION OF
 AIR FROM SUCH SPACES SHALL BE PROHIBITED. ALL AIR
 SUPPLIED TO SUCH SPACES SHALL BE EXHAUSTED, INCLUDING
 ANY AIR IN EXCESS OF THAT REQUIRED BY TABLE 403.3). H)
 FOR NAIL SALONS, THE REQUIRED EXHAUST SHALL INCLUDE
 VENTILATION TABLES OR OTHER SYSTEMS THAT CAPTURE THE
 CONTAMINANTS AND ODORS AT THEIR SOURCE AND ARE CAPABLE
 OF EXHAUSTING A MINIMUM OF 50 CFM PER STATION. THIS
 REQUIREMENT APPLIES TO BOTH MANICURE AND PEDICURE
 STATIONS. PLEASE REVISE THE PLANS ACCORDINGLY.
 2) THE SUBMITTED PLAN SHOWS A NEW O/A INTAKE PROVIDING
 680 CFM TO THE AHU. PROVIDE A VENTILATION CALCULATION
 IN ACCORDANCE WITH TABLE 403.3 TO VERIFY THE MINIMUM
 RATE COMPLIANCE.
 3) INDICATE ON THE PLAN THE AIR INTAKE OPENING WILL BE
 LOCATED TO MEET OR EXCEED THE REQUIRED CLEARANCE
 DISTANCES OUTLINED IN SECTION 401.4.1, AND THE OPENING
 WILL BE PROTECTED IN COMPLIANCE WITH 401.5. PROVIDE TWO
 COPIES OF A FLORIDA PRODUCT APPROVAL OR MIAMI-DADE NOA
 FOR THE INTAKE LOUVER.
 4) A COMPLETE REVIEW OF THE PROJECT CANNOT BE COMPLETED
 AT THIS TIME DUE TO THE LACK OF DETAILS ON THE
 SUBMITTED PLANS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved