Plan Review Notes
Plan Review Notes For Permit 15060791
Permit Number 15060791
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2015-06-22 14:08:52THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF
 THE 5TH EDITION OF FLORIDA FIRE PREVENTION CODE
 INCLUDING THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND
 ALL OTHER APPLICABLE CODES OR STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
  
 2) A DOOR SCHEDULE, INCLUDING HARDWARE IS NOT PROVIDED.
  
 3) THE BATHROOM DOOR OPENS AND RESTRICTS THE MEANS OF
 EGRESS. IT SHALL SWING INTO THE BATHROOM. NFPA 101
 CHAPTER 7, MEANS OF EGRESS
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE
 REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY,
 OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT
 MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A
 CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN,
 UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS
 PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED
 WIDTH OF THE STAIR LANDING WHEN THE DOOR LEAF IS FULLY
 OPEN.
  
 4) AN EXIT LIGHT SHALL BE INSTALLED AT THE REAR DOOR.
  
 5) AN EXIT LIGHT SHALL BE INSTALLED LEADING INTO THE
 REAR EXIT CORRIDOR.
  
 6) THE NATURE OF THE REMODE, IF EXISTING,L REQUIRES AN
 EVALUATION OF THE FIRE ALARM AND SPRINKLER SYSTEM FOR
 CODE COVERAGE AND COMPLIANCE. ANY REMOVAL AND/OR
 CONSTRUCTION OF WALLS REQUIRES AN EVALUATION. PLEASE
 PROVIDE A NOTE INDICATING ANY EXISTING SYSTEM(S).
 IF EXISTING, THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR
 FIRE SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
 IF INDICATED, ANY AND ALL WORK ON THE FIRE ALARM AND
 FIRE SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE
 SHOP DRAWINGS AND BY CERTIFIED LIFE SAFETY CONTRACTORS.
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
  