| 2015-06-22 14:08:52 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF |
| | THE 5TH EDITION OF FLORIDA FIRE PREVENTION CODE |
| | INCLUDING THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND |
| | ALL OTHER APPLICABLE CODES OR STANDARDS. |
| | FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 13, 2010 EDITION. |
| | FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 72, 2010 EDITION. |
| | CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 241, 2009 EDITION. |
| | FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 10, 2010 EDITION. |
| | ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION. |
| | |
| | 2) A DOOR SCHEDULE, INCLUDING HARDWARE IS NOT PROVIDED. |
| | |
| | 3) THE BATHROOM DOOR OPENS AND RESTRICTS THE MEANS OF |
| | EGRESS. IT SHALL SWING INTO THE BATHROOM. NFPA 101 |
| | CHAPTER 7, MEANS OF EGRESS |
| | 7.2.1.4.3 DOOR LEAF ENCROACHMENT |
| | 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS |
| | OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE |
| | REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY, |
| | OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT |
| | MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A |
| | CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN, |
| | UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET: |
| | (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN |
| | EXISTING BUILDING. |
| | (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS |
| | PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED |
| | WIDTH OF THE STAIR LANDING WHEN THE DOOR LEAF IS FULLY |
| | OPEN. |
| | |
| | 4) AN EXIT LIGHT SHALL BE INSTALLED AT THE REAR DOOR. |
| | |
| | 5) AN EXIT LIGHT SHALL BE INSTALLED LEADING INTO THE |
| | REAR EXIT CORRIDOR. |
| | |
| | 6) THE NATURE OF THE REMODE, IF EXISTING,L REQUIRES AN |
| | EVALUATION OF THE FIRE ALARM AND SPRINKLER SYSTEM FOR |
| | CODE COVERAGE AND COMPLIANCE. ANY REMOVAL AND/OR |
| | CONSTRUCTION OF WALLS REQUIRES AN EVALUATION. PLEASE |
| | PROVIDE A NOTE INDICATING ANY EXISTING SYSTEM(S). |
| | IF EXISTING, THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR |
| | FIRE SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE |
| | CONSTRUCTION PERIOD. |
| | IF INDICATED, ANY AND ALL WORK ON THE FIRE ALARM AND |
| | FIRE SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE |
| | SHOP DRAWINGS AND BY CERTIFIED LIFE SAFETY CONTRACTORS. |
| | ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, |
| | SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE |
| | WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL |
| | AND COMPLETE PROTECTION IS RETURNED. |
| | |
| | |