| Notes |
| Date |
Text |
| 2015-07-08 12:03:49 | 1ST REVIEW: FBC 2010 MECHANICAL | | | | | | 1) PROVIDE COOLING AND HEATING LOAD CALCULATIONS FOR | | | THE NEW AC SYSTEM IN ACCORDANCE WITH ACCA MANUAL N OR | | | THE ACCA/ASHRAE STANDARD 183- SECTION 503.2.1 FBC-10 | | | ENERGY CONSERVATION. | | | 2) INDICATE THE LOCATION OF THE NEW CONDENSER AND | | | PROVIDE WIND LOAD TIE DOWN ENGINEERING IN ACCORDANCE | | | WITH SECTION 301.12 FBC-10 MECHANICAL. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|