2015-07-22 17:25:11PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
 1. CORRECT NOTES #7, 16, 17 & 30 ACCORDINGLY: ROMEX IS
 A BRAND NAME AND NOT A RECOGNIZED CABLE TYPE. USE NM,
 NMC, OR MNS IN PLACE THEREOF.
 2. ALL CEILING MOUNTED LUMINAIRE OUTLETS SHALL BE
 LISTED TO SUPPORT 50 LBS, PER NEC 314.27.
 3.THE LOAD ANALYSIS AS SUBMITTED DOES NOT MATCH WITH
 THE SQUARE FOOTAGE STATEMENT OF PAGE A-2.
 4. CORRECT AND EXPLAIN ON THE RISE DIAGRAM:
 A) WHAT IS CAM AT THE METER.
 B) ROUTE OF RACEWAY BETWEEN METER AND PANEL A. THIS
 WILL DETERMINE THE NEED FOR A MAIN DISCONNECT OUTSIDE.
 5. GROUND SERVICE PER NEC AT METER SOCKET.
 6. INCLUDE ON THE RISER THE INTER-SYSTEM BONDING
 TERMINAL REQUIRED BY NEC 250.94.
 7. IF NOT ALREADY IN PLACE, SMOKE DETECTORS AS PER
 FBC-R 314, WILL BE REQUIRED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  