| Date |
Text |
| 2015-07-22 17:25:11 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE |
| | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO |
| | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE |
| | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. |
| | 1. CORRECT NOTES #7, 16, 17 & 30 ACCORDINGLY: ROMEX IS |
| | A BRAND NAME AND NOT A RECOGNIZED CABLE TYPE. USE NM, |
| | NMC, OR MNS IN PLACE THEREOF. |
| | 2. ALL CEILING MOUNTED LUMINAIRE OUTLETS SHALL BE |
| | LISTED TO SUPPORT 50 LBS, PER NEC 314.27. |
| | 3.THE LOAD ANALYSIS AS SUBMITTED DOES NOT MATCH WITH |
| | THE SQUARE FOOTAGE STATEMENT OF PAGE A-2. |
| | 4. CORRECT AND EXPLAIN ON THE RISE DIAGRAM: |
| | A) WHAT IS CAM AT THE METER. |
| | B) ROUTE OF RACEWAY BETWEEN METER AND PANEL A. THIS |
| | WILL DETERMINE THE NEED FOR A MAIN DISCONNECT OUTSIDE. |
| | 5. GROUND SERVICE PER NEC AT METER SOCKET. |
| | 6. INCLUDE ON THE RISER THE INTER-SYSTEM BONDING |
| | TERMINAL REQUIRED BY NEC 250.94. |
| | 7. IF NOT ALREADY IN PLACE, SMOKE DETECTORS AS PER |
| | FBC-R 314, WILL BE REQUIRED. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |