| 2015-11-24 11:31:53 | BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 15060717 |
| | W. P. B. PERMIT: 14110854 |
| | ADD: 5335 N. MILITARY TRAIL |
| | CONT: SISCA CONSTRUCTION |
| | TEL: (561)864-4779 |
| | E-MAIL: ???????????????? |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | E-MAIL SENT TO: |
| | DATE: MON. NOV. 23/2015 |
| | ACTION: DENIED |
| | |
| | E-MAIL SENT TO: DOREEN HAIR |
| | , |
| | DOREEN, |
| | I'VE PULLED THE PLANS AND FOUND NEW CALCULATIONS DATED |
| | 11/13/15. EVERYTHING LOOKED GOOD UNTIL I GOT TO PAGES |
| | 18 & 19 WIND LOAD CERTIFICATIONS PREPARED BY PAUL WELCH |
| | P.E. THESE DOCUMENTS WERE COPIED. ON THE SHEETS YOU CAN |
| | SEE PART OF THE ENGINEER'S (PAUL WELCH) EMBOSSED SEAL |
| | AND SIGNATURE, THEN DAVID SANSOTTA SIGNED AND SEALED |
| | ANOTHER ENGINEER'S WORK!!!!!!! THAT IS A NO,NO!!!!!! IF |
| | MR. SANSOTTA IS NOT THE ENGINEER OF RECORD FOR THE |
| | PROJECT. IF HE IS TO INCLUDE ANOTHER ENGINEERS WORK |
| | WITHIN THE REPORT IT NEEDS TO BE ORIGINALS AND SO |
| | NOTED. THE STRUCTURAL SHEETS WERE SIGNED AND SEALED BY |
| | DAVID MULLINS THE ARCHITECT. MR. MULLINS IS THE ONE |
| | THAT SHOULD PUT THEIR SHOP DRAWING STAMP OF APPROVAL ON |
| | ALL OF THE DOCUMENTS BY BOTH ENGINEERS. |
| | |
| | |
| | JAMES A. WITMER CBO |