| Plan Review Notes For Permit 15060686 |
| Permit Number |
15060686 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2016-05-11 10:26:49 | PLAN | | | REVIEW COMMENTS | | | | | | 4TH REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS | | | FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 | | | THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT | | | APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION | | | INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR THE | | | STRUCTURAL WINDOW MULLIONS. | | | | | | 2) THE PRODUCT APPROVALS FOR THE MODIFIED ROOFING FOR | | | THE SECOND FLOOR COVERED PATIO IS FOR USE OVER | | | CEMENTITIOUS WOOD FIBER AND THE PLANS INDICATE THIS AS | | | A CDX PLYWOOD DECK. SUBMIT PRODUCT APPROVAL FOR WOOD | | | DECK. SIGNED AND SEALED RAS 117 CALCULATIONS WILL ALSO | | | BE REQUIRED IF THE DESIGN UPLIFT PRESSURE OF THE | | | ASSEMBLY REQUIRES ENHANCED FASTENING IN THE PERIMETER | | | AND CORNER AREAS. | | | | | | 3) BOTH SETS OF PLANS ARE MISSING THE STRUCTURAL SHEETS | | | A.7, A.8 AND A.9. FBC 107.1 | | | | | | |
|