| 2016-01-21 10:35:44 | YOUR RESUBMITTAL ADDRESSING THE PREVIOUSLY MENTIONED |
| | DEFICIENCIES HAS ONCE AGAIN FAILED THE ELECTRICAL |
| | REVIEW AS INDICATED BELOW. NEW COMMENTS IF ANY PROMPTED |
| | BY ANOTHER REVIEW, MOST LIKELY DUE TO YOUR FAILURE TO |
| | SUBMIT A RESPONSE LETTER (NARRATIVE) ADDRESSING THE |
| | REQUIRED CORRECTIONS WILL BE NUMBERED IN CONTINUATION |
| | OF ANY PREVIOUS COMMENTS. |
| | |
| | THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE |
| | EDITION OF THE NEC, (NATIONAL ELECTRICAL CODE) AND THE |
| | FBC, (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF |
| | WEST PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. |
| | |
| | IN A TELEPHONE CONVERSATION WITH MR. LES CZACZYK OF LCA |
| | I WAS PROMPTED TO ISSUE THIS WITH A PROVISO, BUT LATER |
| | REALIZED THAT NONE OF THE TRADES COMMENTS FROM PRIOR |
| | REVIEWS HAD BEEN ADDRESSED SO I DECIDED TO ISSUE THE |
| | NOTES FOR THE REQUIRED CORRECTIONS AS PREVIOUSLY |
| | MENTIONED SO THAT THE PLANS CAN ALL GET CORRECTED |
| | PROPERLY. |
| | |
| | 1. CARBON MONOXIDE DETECTORS HAVE NOT ADDED TO THE |
| | PLANS. REVISE PLANS TO SHOW PROPER COVERAGE. |
| | 2. COMMENTS 5 & 6 REFER TO LOAD CALCS AND PANEL |
| | SCHEDULES. THE PANEL SCHEDULE AS INDICATED ON THE |
| | DRAWINGS REFLECTS CIRCUITS FOR THE CONDENSING UNITS IN |
| | PANEL ?A? AS WELL AS MAIN FOR SAME IN THE SPLIT BUS |
| | EXTERIOR PANEL. BEING THAT YOU HAVE THIS ARRANGEMENT, |
| | LOAD CALCS WILL VARY FROM PANEL SCHEDULES. SUBMIT AS |
| | REQUIRED. |
| | 3. THE PREVIOUSLY DISCUSSED MISSING INTER-SYSTEM |
| | BONDING TERMINAL PER NEC 250.94 HAS NOT BEEN ADDED TO |
| | THE SERVICED RISER. |
| | 4. ADD A NOTE TO THE PLANS ADDRESSING THE NEC 406.8(B) |
| | REQUIREMENT FOR WEATHER RATED RECEPTACLES IN WET |
| | LOCATIONS. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE |
| | THE CORRECTIONS ARE ON ALONG WITH THE STANDARD CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | PH: 561-805-6746 |
| | EMAIL: [email protected] |
| | |