| 2015-08-04 09:00:33 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC 2010 |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY MECHANICAL |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| | THE PERSON RESPONSIBLE FOR THE DESIGN. THE PRINTED |
| | NAME, SIGNATURE AND LICENSE NUMBER OF THE SYSTEM |
| | DESIGNER IS REQUIRED ON THE MECHANICAL DRAWINGS. |
| | |
| | 2) FBC-R - M 1602.4 PROVIDE BALANCED AIR RETURN AT |
| | BEDROOMS. TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING |
| | THE RETURN TRANSFER 1-1/2 TIMES THE CROSS SECTIONAL |
| | AREA (SQUARE INCHES) OF THE SUPPLY DUCT ENTERING THE |
| | ROOM OR SPACE IT IS SERVING AND THE DOOR HAVING AT |
| | LEAST AN UNRESTRICTED 1 INCH UNDERCUT TO ACHIEVE PROPER |
| | RETURN AIR BALANCE. THERE IS NO RETURN SHOWN FOR THE |
| | FIRST FLOOR MASTER BEDROOM AND THE TRANSFER DUCT FOR |
| | BEDROOM #2 IS NOT 1-1/2 TIMES THE CROSS SECTIONAL AREA |
| | (SQUARE INCHES) OF THE SUPPLY DUCT ENTERING THE ROOM. |
| | THE TRANSFER DUCT FOR THE SECOND FLOOR MASTER BEDROOM |
| | IS NOT 1-1/2 TIMES THE CROSS SECTIONAL AREA (SQUARE |
| | INCHES) OF THE 12" SUPPLY DUCT SUPPLYING THE MASTER |
| | SUITE ( ALL SUPPLY AIR INTO THE MASTER SUITE SHALL BE |
| | INCLUDED ). |
| | |
| | 3) SOME OF THE INFORMATION LISTED IN THE ENERGY |
| | COMPLIANCE FORMS IS INCORRECT OR MISSING. THERE ARE 5 |
| | BEDROOMS LISTED ON THE FORMS/SIZING CALCULATIONS AND |
| | ONLY 4 BEDROOMS ARE SHOWN ON THE PLANS. ONLY ONE WATER |
| | HEATER IS LISTED ON THE FORMS AND TWO ARE SHOWN ON THE |
| | PLANS (ONE ON EACH FLOOR). THE INSULATED WALLS AND |
| | FLOOR/CEILING ASSEMBLY ADJACENT TO THE GARAGE ARE NOT |
| | LISTED ON THE ENERGY FORMS. THE INSULATION IN THE |
| | CEILING OF THE FIRST FLOOR BEDROOM THAT IS BELOW THE |
| | SECOND FLOOR COVERED PORCH DOES NOT APPEAR TO BE |
| | INCLUDED ON THE FORMS. FBC ENERGY CONSERVATION SEC. 405 |
| | |
| | |
| | |
| | |
| | |
| | |