| Plan Review Notes For Permit 15060678 |
| Permit Number |
15060678 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-07-22 18:10:31 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS | | | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE | | | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO | | | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE | | | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. | | | 1. NEC 600.6, REQUIRES THE EACH SIGN HAVE A DISCONNECT. | | | 2. NEC 600.6(A) REQUIRES THAT THE DISCONNECT BE WITHIN | | | SIGHT OF THE SIGN. | | | 3. NEC ARTICLE 600 HAS SPECIFIC ELECTRICAL REQUIREMENTS | | | FOR SIGNS. | | | 4. FBC-E 505 HAS SPECIFIC SWITCHING REQUIREMENTS FOR | | | SIGNS. | | | | | | ALL OF THE ABOVE SHALL BE COMPLIED WITH AND REFLECTED | | | ON THE ELECTRICAL PAGE FOR THIS PERMIT APPLICATION. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | | | | THANK YOU | | | |
|