| 2015-06-17 12:56:06 | 6/17/2015 |
| | PROJECT: PV SYSTEM |
| | PERMIT#: 15060658 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| | COMMENTS: |
| | |
| | 1) PROVIDE A DETAIL INDICATING HOW THE 60 AMP CIRCUIT |
| | ORIGINATES AT THE UTILITY. THE RISER DIAGRAM |
| | ILLUSTRATES 4, #6 WIRES ORIGINATING AT THE UTILITY BUT |
| | DO NOT ILLLUSTRATE HOW THAT IS IS TO BE ACCOMPLISHED OR |
| | WHAT TYPE OF WIRING METHOD IS UTILIZED FOR THE |
| | INSTALLATION OF THE #6 WIRE TO THE NEW PV PANEL. NEC |
| | 408.4 |
| | |
| | 2) PROVIDE A DETAIL FOR THE INSTALLATION OF THE PVC |
| | CONDUIT WITH THE A/C CIRCUTRY FROM THE PV SYSTEM TO THE |
| | NEW PV PANEL. IS IT INSTALLED INSIDE OR OUTSIDE OF THE |
| | DWELLING. |
| | |
| | 3) PROVIDE A GROUNDING DETAIL ILLUSTRATING THE |
| | CONNECTION OF THE ARRAY GROUNDING ELECTRODE CONDUCTOR |
| | TO THE GROUNDING ELECTRODE SYSTEM. |
| | |
| | 4) INDICATE THE INSTALLATION AND USE OF THE REQUIRED |
| | GFI PROTECTION FOR THE ARRAY. NEC 690.5 |
| | |
| | 5) PROVIDE AND INDICATE ALL REQUIRED LABELING FOR PHOTO |
| | VOLTAIC SYSTEMS IN COMPLIANVCE WITH NEC 690. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |