| 2015-06-18 09:32:25 | 1ST REVIEW: FBC 2010 MECHANICAL |
| | PERMIT #15060656 6/18/15 |
| | |
| | 1) ADDITIONAL DETAILS REGARDING THE REFRIGERANT LEAK |
| | DETECTION SYSTEM, AND THE NORMAL AND EMERGENCY |
| | VENTILATION SYSTEMS ARE REQUIRED DUE TO THE CHILLER |
| | UPGRADES- SEE SHEET ME-1 ASHRAE 15-2010 SUMMARY. PER |
| | NOTE 1 IN THE SUMMARY I HAVE RESEARCHED PERMIT RECORDS |
| | BUT HAVE NOT FOUND ANY 2014 PERMITS TO UPGRADE THE |
| | SYSTEMS. |
| | PLEASE PROVIDE THE FOLLOWING INFORMATION IN ACCORDANCE |
| | WITH ASHRAE 15, 34, AND FMC-2010: |
| | A) INDICATE THE REFRIGERANT CHARGE IN LBS FOR CH-1 IN |
| | THE SCHEDULE ON THE SCHEDULE. |
| | B) REFERENCE SECTIONS 1105.6.3 FMC-10- NORMAL |
| | VENTILATION PROCEDURE, AND 1105.6.4 EMERGENCY |
| | CONDITIONS: PROVIDE DATA INCLUDING VENTILATION |
| | CALCULATIONS, EXHAUST FAN SCHEDULES, MAKEUP AIR LOUVER |
| | SIZES ETC. TO VERIFY COMPLIANCE FOR BOTH SYSTEMS. |
| | C) REFERENCE SECTION 8.11.2.1 ASHRAE 15, AND SECTION |
| | 8.6 ASHRAE 34: SHOW THE EXACT LOCATIONS OF THE REQUIRED |
| | REFRIGERANT LEAK DETECTORS INCLUDING MOUNTING HEIGHTS |
| | AND SPACINGS. |
| | D) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE LEAK |
| | DETECTORS REVIEWED AND APPROVED BY THE ENGINEER OF |
| | RECORD. THE SPECS SHALL INDICATE THE DETECTORS WILL |
| | ACTUATE THE ALARM SYSTEM AT THE LOWEST LEVEL OF |
| | TOXICITY MEASURE. PLEASE INCLUDE WHAT THE LEVEL IS |
| | BASED ON EVIDENCE FROM QUALIFIED TEST REPORT SOURCES. |
| | E) PROVIDE A SEQUENCE OF OPERATION DIAGRAM FOR THE LEAK |
| | DETECTION/ ALARM SYSTEM. SHOW THE LOCATIONS OF ALL |
| | ALARM DEVICES- INSIDE AND OUTSIDE THE MACHINERY ROOM, |
| | AND AT THE ROOM ENTRANCE, PLEASE NOTE THE DEVICES SHALL |
| | BE BOTH VISUAL AND AUDIBLE. SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS FOR ANY NEW DEVICES REVIEWED AND |
| | APPROVED BY THE ENGINEER OF RECORD. |
| | 2) PROVIDE STRUCTURAL DETAILS FOR EXTENSION OF THE |
| | CHILLER PAD AS NOTED IN THE SUBMITTED 8-1/2 X11" SCOPE |
| | OF WORK OUTLINE. |
| | 3) PLEASE SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | NEW CHILLER |
| | |
| | |