2015-06-18 09:32:251ST REVIEW: FBC 2010 MECHANICAL
 PERMIT #15060656 6/18/15
  
 1) ADDITIONAL DETAILS REGARDING THE REFRIGERANT LEAK
 DETECTION SYSTEM, AND THE NORMAL AND EMERGENCY
 VENTILATION SYSTEMS ARE REQUIRED DUE TO THE CHILLER
 UPGRADES- SEE SHEET ME-1 ASHRAE 15-2010 SUMMARY. PER
 NOTE 1 IN THE SUMMARY I HAVE RESEARCHED PERMIT RECORDS
 BUT HAVE NOT FOUND ANY 2014 PERMITS TO UPGRADE THE
 SYSTEMS.
 PLEASE PROVIDE THE FOLLOWING INFORMATION IN ACCORDANCE
 WITH ASHRAE 15, 34, AND FMC-2010:
 A) INDICATE THE REFRIGERANT CHARGE IN LBS FOR CH-1 IN
 THE SCHEDULE ON THE SCHEDULE.
 B) REFERENCE SECTIONS 1105.6.3 FMC-10- NORMAL
 VENTILATION PROCEDURE, AND 1105.6.4 EMERGENCY
 CONDITIONS: PROVIDE DATA INCLUDING VENTILATION
 CALCULATIONS, EXHAUST FAN SCHEDULES, MAKEUP AIR LOUVER
 SIZES ETC. TO VERIFY COMPLIANCE FOR BOTH SYSTEMS.
 C) REFERENCE SECTION 8.11.2.1 ASHRAE 15, AND SECTION
 8.6 ASHRAE 34: SHOW THE EXACT LOCATIONS OF THE REQUIRED
 REFRIGERANT LEAK DETECTORS INCLUDING MOUNTING HEIGHTS
 AND SPACINGS.
 D) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE LEAK
 DETECTORS REVIEWED AND APPROVED BY THE ENGINEER OF
 RECORD. THE SPECS SHALL INDICATE THE DETECTORS WILL
 ACTUATE THE ALARM SYSTEM AT THE LOWEST LEVEL OF
 TOXICITY MEASURE. PLEASE INCLUDE WHAT THE LEVEL IS
 BASED ON EVIDENCE FROM QUALIFIED TEST REPORT SOURCES.
 E) PROVIDE A SEQUENCE OF OPERATION DIAGRAM FOR THE LEAK
 DETECTION/ ALARM SYSTEM. SHOW THE LOCATIONS OF ALL
 ALARM DEVICES- INSIDE AND OUTSIDE THE MACHINERY ROOM,
 AND AT THE ROOM ENTRANCE, PLEASE NOTE THE DEVICES SHALL
 BE BOTH VISUAL AND AUDIBLE. SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR ANY NEW DEVICES REVIEWED AND
 APPROVED BY THE ENGINEER OF RECORD.
 2) PROVIDE STRUCTURAL DETAILS FOR EXTENSION OF THE
 CHILLER PAD AS NOTED IN THE SUBMITTED 8-1/2 X11" SCOPE
 OF WORK OUTLINE.
 3) PLEASE SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 NEW CHILLER
  
  
 CHRISTOPHER COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  