| 2015-06-27 16:59:26 | 6/27/2015 |
| | PROJECT: 3916 GREEWOOD RENNOVATION |
| | PERMIT#: 14020194 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW REVISION #15060882 |
| | ACTION: DENIED |
| | |
| | PERMIT# 14020194 INSPECTION RESULTS DATED 03/03/2014 |
| | NOTE FROM DOUG HARVEY: |
| | STOP WORK ORDER ISSUED. WORK BEING DONE |
| | IN ALL TRADES. PLANS AND COMPLETE |
| | PERMITS NEEDED. NO WORK AND NO POWER |
| | UNTIL FULL PERMIT IS ISSUED AND |
| | COMPLETED. ELECTRICAL NOT READY. NO |
| | WIRES AT SERVICE. |
| | |
| | PERMIT #14020194 IS NOT CURRENTLY EXPIRED. AS A RESULT |
| | A NEW PERMIT APPLICATION IS NOT REQUIRED. THE SCOPE OF |
| | WORK HAS CHANGED. THE PERMIT APPLICATION IS CHANGED TO |
| | REVISION #15060882. |
| | |
| | 1) INDICATE WHERE THE SMOKE DETECTORS ARE INSTALLED. |
| | WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A |
| | PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE |
| | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS |
| | LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL |
| | 314 AND 315. |
| | |
| | 2) NEC 210.12, 406.11 |
| | ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER |
| | RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11 |
| | |
| | 3) NEC 210.52(C)(3) BATHROOM BRANCH CIRCUITS. IN |
| | ADDITION TO THE NUMBER OF BRANCH CIRCUITS REQUIRED BY |
| | OTHER PARTS OF THIS SECTION, AT LEAST ONE 20-AMPERE |
| | BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM |
| | RECEPTACLE OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER |
| | OUTLETS. |
| | 3A) NEC 210.52 (D) BATHROOMS. IN DWELLING UNITS, AT |
| | LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED IN |
| | BATHROOMS WITHIN (3 FT) OF THE OUTSIDE EDGE OF EACH |
| | BASIN. THE RECEPTACLE OUTLET SHALL BE LOCATED ON A WALL |
| | OR PARTITION THAT IS ADJACENT TO THE BASIN OR BASIN |
| | COUNTERTOP, OR INSTALLED ON THE SIDE OR FACE OF THE |
| | BASIN CABINET NOT MORE THAN (12 IN.) BELOW THE |
| | COUNTERTOP. |
| | |
| | 4) NEC 210.8 GROUND-FAULT CIRCUIT-INTERRUPTER |
| | PROTECTION FOR PERSONNEL |
| | (A) DWELLING UNITS. ALL 125-VOLT, SINGLE-PHASE, 15- AND |
| | 20-AMPERE RECEPTACLES INSTALLED IN THE LOCATIONS |
| | SPECIFIED IN (1) THROUGH (8) SHALL HAVE GROUND-FAULT |
| | CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL. |
| | (1) BATHROOMS |
| | |
| | 5) WPB AMENDEMNTS TO THE FBC 107.3.5.3 |
| | PROVIDE A PANEL SCHEDULE AND LOAD CALCULATION. EVERY |
| | CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY |
| | IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC |
| | PURPOSE OR USE. NEC 408.4 |
| | |
| | 6) NEC 110.9 |
| | VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS HAS A |
| | FAULT CURRENT RATING THAT IS SUFFICIENT AT NOMINAL |
| | CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE |
| | INTERRUPTED. |
| | |
| | 7) FBC-EXISTING 708.3 RESIDENTIAL OCCUPANCIES. |
| | IN GROUP R-2, R-3, AND R-4 OCCUPANCIES AND BUILDINGS |
| | REGULATED BY THE FLORIDA BUILDING CODE, RESIDENTIAL, |
| | THE REQUIREMENTS OF SECTIONS 708.3.1 THROUGH 708.3.7 |
| | SHALL BE APPLICABLE ONLY TO WORK AREAS LOCATED WITHIN A |
| | DWELLING UNIT. INDICATE WHAT IS EXISTING TO REMAIN AND |
| | WHAT IS PROPOSED TO BE NEW. IT IS NOT CLEAR FROM WHAT |
| | IS SUBMITTED WHAT IS EXISTING AND WHAT IS PROPOSED. |
| | |
| | 8) WPB AMENDMENTS TO FBC 107.3.1 |
| | TWO COPIES OF ALL PLANS AND SPECIFICATIONS ARE REQUIRED |
| | FOR SUBMITTAL WITH AN APPLICATION FOR PERMIT. ONCE |
| | REVIEWED AND READY FOR ISSUANCE, ONE SET TO BE RETAINED |
| | BY THE BUILDING OFFICIAL FOR THE PURPOSE OF RECORD |
| | KEEPING AND THE OTHER TO BE RETURNED TO THE APPLICANT |
| | UPON ISSUANCE OF THE PERMIT. |
| | |
| | 9) WPB AMENDMENTS TO FBC 107.2.1 |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 10) WPB AMENDMENTS TO FBC 107.2.1.4 |
| | QUALITY OF BUILDING PLANS. BUILDING PLANS SHALL BE |
| | DRAWN TO A MINIMUM 1/8 INCH SCALE UPON SUBSTANTIAL |
| | PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |
| 2015-06-23 15:03:11 | NO ELECTRICAL SHOWN ON PLANS. |