| 2015-06-25 15:26:15 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15060628 |
| | ADD: 2403 S. DIXIE HWY. |
| | CONT: BUTLER CONSTRUCTION |
| | TEL: (561)832-9700 |
| | E-MAIL: |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. JUNE 25/ 2015 |
| | ACTION: DENIED |
| | |
| | 1) SHEET S-1 GRID LINE 9/B-C SHOWS (2) EXISTING 8 IN. X |
| | 16 IN. COLUMN, WITH THE REMOVAL OF THE FLOOR SYSTEM AND |
| | FLOOR BEAMS IN THIS AREA, HOW IS LATERAL SUPPORT FOR |
| | THESE COLUMNS TO BE MAINTAINED? 2010 FBC-B 1907.10, |
| | 1907.11 & ACI318. 7.10 & 7.11. |
| | |
| | 2) SHEET D1.2 BETWEEN GRID LINES B & C ON THE EAST |
| | ELEVATION THE CMU LOAD BEARING ( WHICH WAY IS THE ROOF |
| | FRAMING) BLOCK WALL WORK IS BEING REMOVED TO CREATE NEW |
| | WINDOWS. |
| | THE INTERMEDIATE AND UPPER BEAM WERE DESIGNED WITH |
| | BLOCK INFILL TO HELP SUPPORT THE LOADING OF THE BEAM. |
| | IT WAS COMMON PLACE FOR BOTH BEAMS TO BE A (4) BAR |
| | SYSTEM WITH NO HOOPS OR STIRRUPS. HOOPS OR STIRRUPS |
| | WOULD HAVE BEEN PLACED IN A BEAM WHICH WOULD HAVE |
| | OPENINGS BENEATH AND POSSIBLY EVEN Z BARS MAY BE ALSO |
| | INCORPORATED INTO THE DESIGN DEPENDING ON THE LOAD TO |
| | BE CARRIED AND OR SPANS. THE BIG ISSUE IS THE UPPER |
| | BEAMS FOR OPENINGS B-C AND C-D WITH THE ROOF FRAMING |
| | NOT INDICATED WHICH WALLS THEROOF LOADS ARE BEING |
| | TRANSFERRED TOO? ADDITIONAL INFORMATION IS REQUIRED. |
| | 107.2.1.3. |
| | |
| | 3) THE PLANS DO NOT MAKE IT CLEAR IF THE ACTUAL NEW |
| | WINDOWS ARE GOING TO BE PART OF THIS PROJECT, IF SO |
| | PLEASE PROVIDE THE WIND DESIGN CRITERIA. WIND DESIGN |
| | CRITERIA 2010 FBC-B 1609.1.1 DETERMINATION OF WIND |
| | DESIGN- CHAPTER 6 OF ASCE 7-10. |
| | 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| | 1609.3 WIND SPEED CONVERSION |
| | |
| | 3.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| | |
| | 3.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| | |
| | 3.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| | |
| | 3.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| | |
| | 3.5) COMPONENTS & CLADDING PRESSURES POSITIVE & |
| | NEGATIVE TABLE 1609.2(2) . |
| | |
| | 4) NEW WINDOWS AND STORES NEED TO COMPLY WITH: 2010 |
| | FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1 |
| | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY |
| | AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF |
| | PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| | PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) STOREFRONTS |
| | |
| | 5) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC... |
| | |
| | 6) SHEET S-N SHOWS A DETAIL # 3 SHOWING A NEW GUARDRAIL |
| | SYSTEM. THERE IS A NOTE NEW RAILING SEE ARCHITECTURAL |
| | PLANS, WHERE.107.2.1.3 SHOW COMPLIANCE WITH 2010 FBC-B |
| | 1607.7.1 & 1607.7.1.1. |
| | |
| | 7) SHEET D1.1 NOTE # 11 INDICATES THE REMOVAL OF THE |
| | STAIRWAY AND SAVE OR REUSE. THERE IS NO INFORMATION ON |
| | THE STAIR BEING REINSTALLED ON THE STRUCTURAL SHEETS, |
| | HOW WILL EGRESS BE MAINTAINED TO THE MEZZANINE |
| | LEVEL.107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |