| Plan Review Notes For Permit 15060613 |
| Permit Number |
15060613 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-06-29 11:49:43 | APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED | | | PROVISIONALLY. FAILURE TO CORRECT THE LISTED | | | DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED | | | INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION | | | FEE(S). | | | | | | 1) ELECTRIC SIGNS, SECTION SIGNS, AND OUTLINE LIGHTING, | | | FIXED, MOBILE, OR PORTABLE, SHALL BE LISTED AND | | | INSTALLED IN CONFORMANCE WITH THAT LISTING, UNLESS | | | OTHERWISE APPROVED BY SPECIAL PERMISSION. 600.3 | | | LISTING. | | | | | | 2) EACH SIGN AND OUTLINE LIGHTING SYSTEM, OR FEEDER | | | CIRCUIT OR BRANCH CIRCUIT SUPPLYING A SIGN OR OUT-LINE | | | LIGHTING SYSTEM, SHALL BE CONTROLLED BY AN EXTERNALLY | | | OPERABLE SWITCH OR CIRCUIT BREAKER THAT WILL OPEN ALL | | | UNGROUNDED CONDUCTORS WITHIN SIGHT OF THE SIGN NEC | | | 600.6(A)(1) | | | | | | 3) ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 505.1 | | | SHALL HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT | | | OR WHEN NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & | | | TIME CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME | | | SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMING | | | DURING A LOSS OF POWER FOR A MINIMUM OF 10 HOURS. FBC-E | | | 505.2.4 | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] |
|