| Plan Review Notes For Permit 15060612 |
| Permit Number |
15060612 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-09-28 17:09:38 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS | | | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE | | | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO | | | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE | | | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. | | | 1. YOU SHALL SUBMIT A COMPLETE AND SITE SPECIFIC RISER | | | DIAGRAM AS INDICATED IN NEC 210.5. THERE SHALL BE A | | | NOTE RELATING TO THE ARC-FAULT REQUIREMENT OF 110.16 AS | | | WELL. | | | 2. YOU SHALL ALSO PROVIDE LOAD CALCULATIONS AS REQUIRED | | | IN NEC 220.16 | | | 3. YOU SHALL INDICATE WITH CERTAINTY THE LOCATION OF | | | THE SERVICE EQUIPMENT AS REQUIRED BY NEC 230.70 | | | 4. YOU SHALL INDICATE ON THE FLOOR PLAN THE LOCATION OF | | | THE ELECTRICAL PANELS AS REQUIRED BY NEC 240.24 | | | 5. EVERY COMMERCIAL ESTABLISHMENT SHALL HAVE A | | | DEDICATED SIGN OUTLET ABOVE EVERY DOOR USED FOR | | | PEDESTRIAN ACCESS AS MENTIONED IN NEC 600.5 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | | | | THANK YOU | | | |
|