| 2015-06-22 16:41:05 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) DOOR SWING. WHERE SERVING A ROOM OR AREA WITH AN |
| | OCCUPANT LOAD OF 50 OR MORE THE DOOR SHALL SWING IN THE |
| | DIRECTION OF EGRESS TRAVEL. THE FRONT DOOR AND THE |
| | VESTIBULE DOOR SHALL SWING IN THE DIRECTION OF EGRESS. |
| | |
| | 2) PROVIDE A SITE PLAN SHOWING THAT THE PROPOSED EXITS |
| | LEAD TO A PUBLIC WAY. |
| | |
| | 3) NFPA 101 16.3.2.PROTECTION FROM HAZARDS. 16.3.2.1 |
| | ROOMS OR SPACES FOR THE STORAGE, PROCESSING, OR USE OF |
| | MATERIALS SPECIFIED IN 16.3.2.1 (1) THROUGH (3) SHALL |
| | BE OPROTECTED IN ACCORDANCE WITH THE FOLLOWING: |
| | (1) SEPARATION FROM THE REMIADER OF THE BUILDING BY |
| | FIRE BARRIERS HAVING A MINIMUM 1-HOUR FIRE RESISTIVE |
| | RATING, OR PROTECTION OF SUCH ROOMS BY AUTIOMATICE |
| | EXTINGUSHING SYSTEMS AS SPECIFIED IN |
| | SECTION 8.7 IN THE FOLLOWING AREAS: |
| | (D) JANITOR CLOSETS. |
| | PROVIDE FIRE RESISTIVE WALSS AND DOOR TO THE PROPOSED |
| | JANITOR CLOSET. |
| | |
| | 4) PROVIDE INFORMATION PERTAINING TO THE OTHER CAMPUS |
| | BUILDINGS RELATING TO EXISTING FIRE SPRINKLER OF FIRE |
| | ALARM. CONNECTION TO EXISTING BUILDINGS THAT ARE FULLY |
| | SPRINKLERED MAY REQUIRE THAT THIS BUILDING BE |
| | SPRINKLERED DUE TO IT BEING ATTACHED. THE FIRE ALARM |
| | MAY BE REQUIRED TO BE CONNECTED TO THE CAMPUS FIRE |
| | ALARM IF EXISTING. |
| | |
| | 5) PROVIDE THE OCCUPANCIES OF THE OTHER CAMPUS |
| | BUILDINGS. DESCRIBE WHAT IS BEING CONDUCTED IN EACH OF |
| | THE BUILDINGS. |
| | |
| | |