| 2015-06-17 16:46:19 | 6/17/2015 |
| | PROJECT: SWIMMING POOL |
| | PERMIT#: 15060608 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| | COMMENTS: |
| | |
| | 1) PROVIDE A REFFERENCE FOR THE LOAD CALCULATION |
| | SUBMITTED. THE DEMAND LOAD SUBMITTED IS RAZOR CLOSE TO |
| | 100% OF THE MAIN OCPD. PROVIDE SUPPORTING DOCUMENTATION |
| | FOR THE TOTAL DEMAND LOAD ARRIVED AT IN THE |
| | CALCULATION. WPB AMENDMENTS TO THE FBC 107.2.1 |
| | |
| | 2) PROVIDE A PANEL SCHEDULE THAT INCLUDES THE OCPD AND |
| | WIRE SIZES FOR ALL NEW CIRCUITS. NEC 408.4 |
| | |
| | 3) PROVIDE MANUFACTURER SPECS FOR NEW POOL PANEL, TIME |
| | CLOCK, TRANSFORMER, DECK BOX AND POOL LIGHTS. NEC |
| | 680.24, 110.3 |
| | |
| | 4) ALL DESIGN DOCUMENTS TO BE SIGNED BY THE DESIGNER |
| | RESPONSIBLE FOR THE DESIGN. ALL INFORMATION, DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE |
| | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE |
| | DESIGN. FBC, WPB AMENDMENTS 107.2.1 |
| | 4A) THE SUBMITTED PLANS ARE PHOTOCOPIED PLANS OF AN |
| | ORIGINAL SIGNED AND SEALED PLAN. PLANS, SPECIFICATIONS, |
| | REPORTS OR OTHER DOCUMENTS PREPARED BY THE DESIGN |
| | PROFESSIONAL AND BEING FILED FOR PUBLIC RECORD SHALL |
| | HAVE THE SIGNATURE AND SEAL OF THE DESIGN PROFESSIONAL |
| | AFFIXED TO THE DOCUMENT. |
| | FL ADMIN CODE 61G15-23.002 ENGINEERS |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |