| 2015-06-15 12:28:36 | RESIDENTIAL (R2) ALTERATION. BUILDING REVIEW COMMENTS. |
| | CODE: 2010 FBC-BUILDING |
| | |
| | 1- TILE FLOORING IS OUT OF THE SCOPE OF WORK OF A |
| | CARPENTRY CONTRACTOR. THIS CONTRACTOR CAN'T PERFORM |
| | THIS WORK. SEE THE PALM BEACH COUNTY CONSTRUCTION |
| | INDUSTRY LICENSING BOARD STANDARDS FOR CERTIFIED |
| | CATEGORIES FOR SCOPE OF WORK OF EACH LICENSE. CHAPTER |
| | 489 FL. ST. NEED CONTRACTOR WITH PROPER LICENSE TO |
| | APPLY FOR THE PERMIT. |
| | |
| | 2- SOUND INSULATION MATERIAL SUBMITTED: |
| | A) PROVIDE 2 COPIES OF THE FLAME SPREAD INDEX AND SMOKE |
| | DEVELOPED TEST DONE IN ACCORDANCE WITH ASTM E 84 OR UL |
| | 723 AS REQUIRED BY SEC. 719.1 OF 2010 FBC-BUILDING. |
| | |
| | B) PROVIDE 2 COPIES OF THE SOUND TRANSMISSION CLASS |
| | (STC) TEST DONE IN ACCORDANCE WITH ASTM E 90 AS |
| | REQUIRED BY SEC. 1207.2 OF 2010 FBC-BUILDING. |
| | NOTE: TEST SAMPLE TO MATCH BUILDING CONSTRUCTION. THERE |
| | ARE TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT |
| | ACOUSTICAL CEILING. |
| | |
| | C) PROVIDE 2 COPIES OF THE IMPACT INSULATION CLASS |
| | (IIC) TEST DONE IN ACCORDANCE WITH ASTM E 492 AS |
| | REQUIRED BY SEC. 1207.3 OF 2010 FBC-BUILDING. |
| | NOTE: TEST SAMPLE TO MATCH BUILDING CONSTRUCTION. THERE |
| | ARE TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT |
| | ACOUSTICAL CEILING. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | (561)805-6712 |
| | [email protected] |