| 2015-06-27 14:10:28 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15060568 |
| | ADD: 400 N. FLSGLER DR. SUITE 2102 |
| | CONT: MARYJULI CONSTRUCTION |
| | TEL: (561)386-6032 |
| | E-MAIL: |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: SAT. JUNE 27/2015 |
| | ACTION: DENIED |
| | |
| | 1) THE PLANS DO NOT HAVE ANY DESIGN CRITERIA TO WHAT |
| | CODE HAS THE PLANS BEEN DRAWN, UNDER THE EXISTING |
| | BUILDING CODE THE DESIGNER OF RECORD NEEDS TO INDICATE |
| | ON THE PLANS THE COMPLIANCE METHOD FOR THIS DESIGN. |
| | 2010 EXST. BLDG. CODE 101.5. |
| | |
| | 2) THE PLANS DO NOT INDICATE THE BUILDING TYPE NOR THE |
| | RESTRICTIONS ON TYPE I TYPE II CONSTRUCTION. 2010 FBC-B |
| | 603..1 ALLOWABLE MATERIALS. |
| | |
| | 3) THE PLANS INDICATE THERE IS TO BE RAISED CEILINGS IN |
| | THE MASTER BATH, NO DETAILS AS TO HOW THE EXISTING |
| | CEILING/ SOFFIT IS HUNG NOR HOW THE NEW RAISED CEILINGS |
| | ARE TO BE BUILT. 107.3.5.1.1 MINIMUM PLAN REVIEW |
| | CRITERIA FOR COMMERCIAL BUILDINGS. TYPE OF MATERIALS |
| | FOR FRAMING MEMBERS, SIZE OF FRAMING MEMBERS, GAUGE, |
| | SPACING, IF STIFF BACKS ARE REQUIRED TYPE OF FINISH |
| | MATERIAL AND THICKNESS. PLEASE PROVIDE THE FINISH |
| | ELEVATION ABOVE THE FINISH FLOOR. |
| | |
| | 4) THE PERMIT APPLICATION INDICATES TO RENOVATE |
| | BATHROOMS, IF THE FLOORING IS BEING REMOVED PLEASE |
| | PROVIDE COMPLIANCE WITH: |
| | |
| | BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION |
| | |
| | 4A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 4B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 4C) FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 5) THE PLANS INDICATE A NEW SHOWER STALL PLEASE PROVIDE |
| | THE TYPE OF BACKING TO BE REPLACED FOR THE PLACEMENT OF |
| | TILE. 2010 FBC-B |
| | 2509.2 BASE FOR TILE SURFACES. |
| | |
| | 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |