Plan Review Notes
Plan Review Notes For Permit 15060563
Permit Number 15060563
Review Stop M
Sequence Number 2
Notes
Date Text
2015-10-30 11:35:552ND REVIEW: FBC 2010 MECHANICAL
 PERMIT #15060563
 10/30/15
  
 NOTICE!!!!!!!!!!!!! CHAPTER 553.80(2)(B) FLORIDA
 STATUTES STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A
 FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE
 REJECTED (3) OR MORE TIMES FOR REPEATED FAILURE TO
 CORRECT A CODE VIOLATION.
 PLEASE REFER TO COMMENTS FROM THE 1ST REVIEW AND THE
 NARRATIVE RESPONSES. SEVERAL OF THE COMMENTS HAVE NOT
 BEEN ADDRESSED COMPLETELY.
 1) SITE AND CIVIL COMMENT #1: THE RESPONSE NARRATIVE
 REFERENCES DRAWING #0747-C-STD-01 WHICH IS NOT INCLUDED
 IN THE PLAN SET: PLEASE PROVIDE THE DRAWING.
 2) DEWATERING BUILDING COMMENT #1: THE RESPONSE
 NARRATIVE REFERENCES SHEETS M-OCS-1 TO -4 WHICH ARE
 INCLUDED IN THE PLANS SET: PLEASE PROVIDE THE SHEETS.
 3) DEWATERING BUILDING COMMENT #2: THE REQUESTED
 VENTILATION AND AIR BALANCE CALCULATIONS WERE NOT
 SUBMITTED. PLEASE NOTE THAT SHEET H-DEW-05 DOES NOT
 INDICATE HOW THE EXHAUST VENTILATION AND PRESSURIZATION
 SYSTEMS WERE CALCULATED OR SIZED- BY WHAT METHOD OR
 STANDARD?
 4) DEWATERING BUILDING COMMENT #4: PLEASE REFER TO
 SECTIONS 404.1, 404.2, & 404.3 FBC-10 MECHANICAL AND
 SHOW THE LOCATIONS OF THE CO DETECTORS AND EXHAUST
 VENTILATION AND PRESSURIZATION CALCULATIONS.
 404.1 ENCLOSED PARKING GARAGES.
 MECHANICAL VENTILATION SYSTEMS FOR ENCLOSED PARKING
 GARAGES ARE NOT REQUIRED TO OPERATE CONTINUOUSLY WHERE
 THE SYSTEM IS ARRANGED TO OPERATE AUTOMATICALLY UPON
 DETECTION OF A CONCENTRATION OF CARBON MONOXIDE OF 25
 PARTS PER MILLION (PPM) BY APPROVED AUTOMATIC DETECTION
 DEVICES.
 404.2 MINIMUM VENTILATION.
 AUTOMATIC OPERATION OF THE SYSTEM SHALL NOT REDUCE THE
 VENTILATION AIRFLOW RATE BELOW 0.05 CFM PER SQUARE FOOT
 (0.00025 M3/S ? M2) OF THE FLOOR AREA AND THE SYSTEM
 SHALL BE CAPABLE OF PRODUCING A VENTILATION AIRFLOW
 RATE OF 0.75 CFM PER SQUARE FOOT (0.0038 M3/S ? M2) OF
 FLOOR AREA.
 404.3 OCCUPIED SPACES ACCESSORY TO PUBLIC GARAGES.
 CONNECTING OFFICES, WAITING ROOMS, TICKET BOOTHS AND
 SIMILAR USES THAT ARE ACCESSORY TO A PUBLIC GARAGE
 SHALL BE MAINTAINED AT A POSITIVE PRESSURE AND SHALL BE
 PROVIDED WITH VENTILATION IN ACCORDANCE WITH SECTION
 403.3.
 4A) PROVIDE A SUBMITTAL FOR THE CO DETECTOR REVIEWED
 AND APPROVED BY THE ENGINEER OF RECORD.
 5) DEWATERING BUILDING COMMENT #5: AS PREVIOUSLY
 REQUESTED PLEASE SHOW THE REQUIRED DUCT SMOKE DETECTORS
 IN THE MECHANICAL PLAN SHEETS. PLEASE NOTE THAT THE
 UPLOADED SPECIFICATION 15734 IS NOT PART OF THE
 BUILDING PLANS, AND IN THE DOCUMENT IT IS STATED TO
 "PROVIDE SMOKE DETECTOR IN THE SUPPLY AIR". PROVIDE AN
 EQUIPMENT SCHEDULE FOR THE DEVICES ON THE PLAN AND A
 SUBMITTAL REVIEWED AND APPROVED BY THE ENGINEER OF
 RECORD.
 6) DEWATERING BUILDING COMMENT #8 AND #15: DEFERRED
 SUBMITTAL: 107.3.4.2 DEFERRED SUBMITTALS. FOR THE
 PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL
 OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF
 THE BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR
 REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING (FANS, FIRE DAMPERS, SMOKE
 DETECTORS, CO DETECTORS, O/A DAMPERS, CONTROLS, ETC.)
 DEFERRED SUBMITTAL. 2010 FBC 107.3.4.1 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL (AC STANDS, FANS AND
 LOUVERS).
 NOTE: AS PREVIOUSLY COMMENTED, SITE SPECIFIC WIND LOAD
 ENGINEERING FOR ATTACHMENT OF THE FANS, FAN CURBS, AND
 AC UNITS IS REQUIRED PER SECTION 301.13. THE DETAILS ON
 SHEET H-STD-3 ARE INCOMPLETE AND NOT IN COMPLIANCE.
 7) DEWATERING BUILDING COMMENT #14: CONTRART TO THE
 NARRATIVE RESPONSE, UL APPROVED FIRESTOPPING DETAILS
 ARE TYPICALLY SHOWN ON CONSTRUCTION DRAWINGS, AND ARE
 ALSO REQUIRED BY WPB BUILDING DEPARTMENT TO BE ON THE
 PLANS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  