| 2015-11-05 11:28:14 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15060563 CENTRIFUGE DEWATERING |
| | BUILDING |
| | ADD: 4395 EASLEY ST. |
| | CONT: TBD/ TO BE DETERMINED |
| | CONTACT: KURT PFEFFER, P. E. |
| | TEL: (561)997-8070 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2ND REVIEW |
| | DATE: THURS. NOV. 05/ 2015 |
| | ACTION: DENIED |
| | |
| | NOTE: SPECIFICATION BOOKS WILL NOT BE REVIEWED AS PART |
| | OF ANY PLAN REVIEW IF SUBMITTED THEY GET STAMPED VOID. |
| | |
| | 1-4) COMPLIED. |
| | |
| | |
| | 5) MISSING INFORMATION ENERGY FORMS 2010 FBC-ENERGY |
| | 103.2 ENERGY REPORTING FORMS. INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. 103.2.1 CODE DEMONSTRATION |
| | FORMS. SEE TABLE 103.2.1. PLANS ARE MISSING THE |
| | REQUIRED INSULATION BY THE 2010 FBC-ENERGY 502 BUILDING |
| | ENVELOPE REQUIREMENTS OR 506 TOTAL BUILDING |
| | PERFORMANCE. |
| | |
| | 6) PROVISO: 2010 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION |
| | 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS |
| | SECTION, DEFERRED SUBMITTALS ARE |
| | DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT |
| | SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE |
| | TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A |
| | SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL |
| | HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE |
| | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| | SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION |
| | DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 |
| | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY |
| | AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF |
| | PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| | PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS & ROOF HATCH. |
| | (B) WINDOW |
| | (C), WALL LOUVERS, EFIS SYSTEMS |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, CURBS |
| | (E) PRE-ENGINEERED A/C STANDS IF ROOF TOP |
| | |
| | 7) PROVISO: 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | |
| | 8) 2ND REQUEST. SHEET 0312- S-DEW-06 PRESSURES FOR |
| | COMPONENTS AND CLADDING EXPOSURE "C" @ 180 MPH, 60 FT. |
| | ABOVE GRADE, ARE LOW FOR BOTH THE ROOF ZONES AND WALL |
| | ZONES. MULTIPLIER OF 1.62 FOR HEIGHT FOR VULT |
| | PRESSURES. PLEASE NOTE THAT THE NEGATIVE ROOF PRESSURES |
| | ARE TO BE TAKEN FROM THE HIGHEST ROOF. THE PRESSURES |
| | PROVIDED IN BOTH TABLES STATE THEY WERE TAKEN AT THE |
| | LOWER PUMP ROOF ELEVATION. |
| | 2ND REQUEST, PLEASE ALSO SUPPLY PRESSURES IN VASD SINCE |
| | ALL PRODUCT APPROVALS ARE IN VASD. |
| | |
| | 10SQ. FT. 180MPH EXP. C @ ELE. 60 FT. |
| | APPROXIMATE PRESSURES +/- |
| | VULT VASD |
| | ZONE 1 - 94.44 - 56.66 |
| | ZONE 2 - 158.4 -95.06 |
| | ZONE 3 3 FT + PARAPET SAME AS ZONE 2 |
| | ZONE4 - 102.38 -61.4 |
| | ZONE 5 -126.36 -75.8 |
| | |
| | 9-16) COMPLIED |
| | |
| | 17)2ND REQUEST. SHEET 0409-A-DEW-16. SHOWS A EXTERIOR |
| | STAIR, GUARDRAIL / HANDRAIL SYSTEM THERE IS A NOTE |
| | INDICATING SEE 4/ A-DEW-29, THIS WAS A MISSING SHEET. |
| | THE PLAN SUBMITTED THIS ROUND DOES NOT HAVE ANY OF THE |
| | REQUESTED HANDRAIL/ GUARDRAIL INFORMATION TO REVIEW FOR |
| | CODE COMPLIANCE. 107.2.1.3 ADDITIONAL INFORMATION IS |
| | REQUIRED. 107.3.5.1.1 MINIMUM PLAN REVIEW CRITERIA FOR |
| | COMMERCIAL BUILDINGS. |
| | 2010 FBC-B 1012 HANDRAILS & 1013 GUARDRAILS. |
| | |
| | 18 COMPLIED. |
| | |
| | 19) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |