Plan Review Notes
Plan Review Notes For Permit 15060563
Permit Number 15060563
Review Stop P
Sequence Number 1
Notes
Date Text
2015-07-20 10:57:441) SUBMIT THE TYPE OF OCCUPANCY AND THE OCCUPANT LOAD
 FOR THIS BUILDING. WPB AMEND. TO FBC SEC. 107.2.1.
 2) SHT.M-DEW-02 - SHOWS A SAMPLING SINK. INDICATE ON
 THE PLANS IF ANY WASTES DETRIMENTAL TO THE PLUMBDING
 SYSTEM WILL BE TESTED/SAMPLED AT THIS LOCATION.FPC
 SEC.803.2.
 3) THE BREAKROOM SINK SHALL COMPLY WITH THE FAC
 SEC.212.2.
 4) INTERMEDIATE LEVEL 42.00 - THERE SHALL BE ONE
 HANDICAP ACCESSIBLE STALL IN THE WOMEN'S RESTROOM AND
 ONE IN THE MEN'S RESTROOM AND ONE SHOWER IN THE WOMEN'S
 AND MEN'S RESTROOM SHALL BE HANDICAP ACCESSIBLE PER
 2010 FAC SECS.213.1, 213.2, 213.3.1.
 5) SHEET M-DEW-13 - A MINIMUM OF TWO DRINKING FOUNTAINS
 ARE REQUIRED PER THE FAC SEC. 211.2. THE CUP DISPENSER
 SHOWN ON A-DEW-26, DETAILA-6 IS NOT ACCEPTABLE.
 6) TOILET FACILITIES SHALL NOT BE LOCATED ONE STORY
 ABOVE OR BELOW THE SPACE REQUIRED TO BE PROVIDED WITH
 TOILET FACILITIES AND THE PATH OF TRAVEL SHALL NOT
 EXCEED 500 FT. FPC SEC. 403.3.2.
 7) SHT. A-DEW-22 - THE WASTE FROM THE SUMP IN THE
 ELEVATOR PIT SHALL DISCHARGE THROUGH AN OIL SEPARATOR
 IN ACCORDANCE WITH FPC SEC. 1003.4.
 8) SHT. 0419 -A-DEW-26 - ENLARGED ACCESSIBLE TOILET
 ROOM PLAN - CLEALY SHOW THE DIMENSION FROM THE CLOSEST
 INTERIOR FINISH WALL TO THE CENTERLINE OF THE
 ACCESSIBLE TOILET. COMPLY WITH FAC SEC.604.2 & FIGURE
 604.2.
 9) SUBMIT THE CIVIL DRAWINGS FOR THIS BUILDING.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  