| Date |
Text |
| 2015-07-20 10:57:44 | 1) SUBMIT THE TYPE OF OCCUPANCY AND THE OCCUPANT LOAD |
| | FOR THIS BUILDING. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 2) SHT.M-DEW-02 - SHOWS A SAMPLING SINK. INDICATE ON |
| | THE PLANS IF ANY WASTES DETRIMENTAL TO THE PLUMBDING |
| | SYSTEM WILL BE TESTED/SAMPLED AT THIS LOCATION.FPC |
| | SEC.803.2. |
| | 3) THE BREAKROOM SINK SHALL COMPLY WITH THE FAC |
| | SEC.212.2. |
| | 4) INTERMEDIATE LEVEL 42.00 - THERE SHALL BE ONE |
| | HANDICAP ACCESSIBLE STALL IN THE WOMEN'S RESTROOM AND |
| | ONE IN THE MEN'S RESTROOM AND ONE SHOWER IN THE WOMEN'S |
| | AND MEN'S RESTROOM SHALL BE HANDICAP ACCESSIBLE PER |
| | 2010 FAC SECS.213.1, 213.2, 213.3.1. |
| | 5) SHEET M-DEW-13 - A MINIMUM OF TWO DRINKING FOUNTAINS |
| | ARE REQUIRED PER THE FAC SEC. 211.2. THE CUP DISPENSER |
| | SHOWN ON A-DEW-26, DETAILA-6 IS NOT ACCEPTABLE. |
| | 6) TOILET FACILITIES SHALL NOT BE LOCATED ONE STORY |
| | ABOVE OR BELOW THE SPACE REQUIRED TO BE PROVIDED WITH |
| | TOILET FACILITIES AND THE PATH OF TRAVEL SHALL NOT |
| | EXCEED 500 FT. FPC SEC. 403.3.2. |
| | 7) SHT. A-DEW-22 - THE WASTE FROM THE SUMP IN THE |
| | ELEVATOR PIT SHALL DISCHARGE THROUGH AN OIL SEPARATOR |
| | IN ACCORDANCE WITH FPC SEC. 1003.4. |
| | 8) SHT. 0419 -A-DEW-26 - ENLARGED ACCESSIBLE TOILET |
| | ROOM PLAN - CLEALY SHOW THE DIMENSION FROM THE CLOSEST |
| | INTERIOR FINISH WALL TO THE CENTERLINE OF THE |
| | ACCESSIBLE TOILET. COMPLY WITH FAC SEC.604.2 & FIGURE |
| | 604.2. |
| | 9) SUBMIT THE CIVIL DRAWINGS FOR THIS BUILDING. |
| | |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |
| | |