| 2015-07-06 07:26:43 | 1ST REVIEW: FBC 2010 MECHANICAL |
| | PERMIT #15060563 CENTRIFUGE DEWATERING BUILDING- 7/2/15 |
| | |
| | SITE AND CIVIL: NO DRAWINGS SUBMITTED. |
| | 1) BASED ON THE SOILS REPORT- PIPE BEDDING AND |
| | DEWATERING GUIDELINES, PLEASE PROVIDE PIPE TRENCH |
| | CROSS-SECTION DETAILS FOR TYPICAL INSTALLATIONS AND |
| | HIGH WATER TABLE INSTALLATIONS. INDICATE TRENCH |
| | DIMENSIONS, PIPE EMBEDMENT DEPTHS, BEDDING MATERIALS |
| | AND THICKNESSES, COMPACTION AND BACKFILLING |
| | SPECIFICATIONS. |
| | 2) PROVIDE CIVIL DRAWINGS THAT INCLUDE OVERALL |
| | UNDERGROUND PIPING LAYOUTS, AND ENLARGED AREA DRAWINGS |
| | DEPICTING THE UNDERGROUND PIPINGS SERVICING EACH TANK, |
| | FACILITY, OR BUILDING. |
| | |
| | SPECIFIC COMMENTS TO THE DEWATERING BUILDING MECHANICAL |
| | AND HVAC SYSTEMS: |
| | 1) PROVIDE ADDITIONAL DETAILS AND NOTES FOR THE FOUL |
| | AIR (FA) SYSTEMS CLARIFYING HOW THE AIR IS BEING |
| | EXHAUSTED FROM THE EQUIPMENT AND TRANSFERRED TO THE |
| | ODOR CONTROL SCRUBBER- REFERENCE SHEETS M-DEW-08 & 10. |
| | PROVIDE EQUIPMENT SCHEDULES FOR ALL COMPONENTS OF THE |
| | EXHAUST SYSTEM- FANS, DUCTS, DAMPERS ETC. SHOW THE |
| | LOCATIONS OF THE EXHAUST FANS, SHOW DUCT CONNECTION AND |
| | SUPPORT DETAILS, AND SHOW THE UNDERGOUND DUCT RUNS. IF |
| | THE DETAILS ARE CONTAINED IN THE CIVIL DRAWINGS, THEN |
| | PLEASE INCLUDE THE APPLICABLE SHEETS WITH THE PLAN SETS |
| | FOR THIS PERMIT |
| | 2) PROVIDE THE FOLLOWING LIST OF CALCULATIONS ON THE |
| | PLAN: A) VENTILATION CALCULATIONS FOR ALL ROOMS AND |
| | SPACES IN COMPLIANCE WITH TABLE 403.3 FBC- 10 |
| | MECHANICAL. PROVIDE A TABLE ON THE PLAN SHOWING THE |
| | REQUIRED MINIMUM O/A CFM'S AND THE CFM AMOUNT BEING |
| | PROVIDED. B) EXHAUST VENTILATION CALCULATIONS PERTABLE |
| | 403.3 FBC-10 MECHANICAL, OR TABLE 6-4 ASHRAE 62.1-07. |
| | C) AIR BALANCE CALCULATIONS. |
| | 3) SUBMIT THE FOLLOWING ENERGY EFFICIENCY COMPLIANCE |
| | DOCUMENTS PREPARED BY THE ENGINEER OF RECORD: A) |
| | COOLING AND HEATING CALCULATIONS IN ACCORDANCE WITH |
| | ACCA MANUAL N OR APPROVED ALTERNATE METHOD FOR ALL NEW |
| | AC SYSTEMS TO BE INSTALLED- SECTION 503.2.1 FBC-10 |
| | ENERGY EFFICIENCY. B) ENERGY EFFICIENCY FORM 502-2010 |
| | OR 506-2010. |
| | 4) SHEET H-DEW-1: THE EXHAUST SYSTEM IN THE LOADING |
| | AREA SHALL RUN CONTINUOUSLY OR AUTOMATICALLY UPON |
| | DETECTION OF CARBON MONOXIDE OF 25 PARTS PER MILLION |
| | (PPM) BY APPROVED AUTOMATIC DETECTION DEVICES- SECTION |
| | 404.1 FBC-10 MECHANICAL. REVISE THE PLAN ACCORDINGLY. |
| | 5) SHEETS H-DEW-1, 2, 3, & 4: SHOW THE LOCATIONS OF THE |
| | REQUIRED DUCT SMOKE DETECTORS IN THE SUPPLY AND RETURN |
| | DUCTS- SECTION 606.2.2. INDICATE HOW THE DETECTORS WILL |
| | BE SUPERVISED PER SECTION 606.4.1, AND PROVIDE AN |
| | EQUIPMENT SCHEDULE ON THE PLAN FOR THE DEVICES. |
| | 6) H-DEW-2: INDICATE HOW SUPPLY AIR IS BEING RETURNED |
| | FROM THE CONTROL/OFFICE ROOM AND THE BREAKROOM- SECTION |
| | 601.4. |
| | 7) H-DEW-2: PROVIDE EXHAUST VENTILATION FOR THE WOMEN'S |
| | TOILET/SHOWER ROOMS- TABLE 403.3. |
| | 8) H-DEW-2: ENGINEERED WIND LOAD TIE-DOWN DETAILS FOR |
| | MOUNTING THE CONDENSERS AND ROOF STANDS ON THE LOW ROOF |
| | ARE REQUIRED PER SECTION 301.12. PLEASE PROVIDE |
| | DETAILS, OR PLACE A NOTE INDICATING ON WHICH STRUCTURAL |
| | OR ARCHITECTURAL SHEET THE DETAILS ARE LOCATED. PROVIDE |
| | ELEVATION AND PLAN VIEW DRAWINGS TO INDICATE COMPONENTS |
| | OF THE STANDS, AND THE CONDENSER HEIGHTS ABOVE THE |
| | FINISHED ROOF. IN ADDITION PROVIDE DETAILS FOR |
| | ANCHORING AND SUPPORTING THE REFRIGERANT PIPINGS, AND |
| | THE TYPE AND THICKNESS OF PIPING INSULATION. |
| | 9) H-DEW-3: INDICATE HOW SUPPLY AIR IS BEING RETURNED |
| | FORM THE CONTROLS AREA. |
| | 10) H-DEW-3: PROVIDE A MEANS OF VENTILATION FOR THE |
| | STORAGE ROOM- TABLE 403.3 |
| | 11) H-DEW-3: PROVIDE A FIRE DAMPER FOR THE CASSETTE |
| | SHOWN IN THE FIRE-RATED ELEVATOR MACHINE ROOM WALL. |
| | 12) PROVIDE AN AIR DISTRIBUTION SCHEDULE ON THE PLAN |
| | LISTING MAKES AND MODELS AND SIZES OF ALL COMPONENTS |
| | INCLUDING DUCTS, DIFFUSERS, AND RETURN GRILLS. |
| | 13) PROVIDE TYPICAL DUCT HANGING AND CONNECTION DETAILS |
| | IN ACCORDANCE WITH THE SMACNA 2005 STANDARD. |
| | 14) PROVIDE TESTED AND APPROVED FIRE STOPPING SYSTEM |
| | DETAILS FOR ALL PIPES OR DUCTS PENETRATING FIRE-RATED |
| | WALLS. |
| | 15) PROVIDE A SUBMITTAL PACKAGE THAT INCLUDES A) |
| | FLORIDA PRODUCT APPROVALS AND/OR MIAMI DADE NOA'S FOR |
| | ALL PRODUCTS REGULATED BY FAC RULE 9N-3 REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGN PROFESSIONAL OF |
| | RECORD (CONDENSER STANDS, EXHAUST AND INTAKE LOUVERS |
| | AND FANS ETC.). B) MANUFACTURER'S PRODUCT DATA SHEETS |
| | FOR THE AC SYTEMS, EXHAUST FANS, FIRE DAMPERS, DUCT |
| | SMOKE OR CARBON MONOXIDE DETECTORS, O/A MOTORIZED |
| | DAMPERS, ELECTRONIC CONTROLS, PIPINGS, PIPE FIOTTINGS |
| | AND INSULATION ETC. |
| | |