2015-07-06 09:23:52BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15060563 CENTRIFUGE DEWATERING
 BUILDING
 ADD: 4395 EASLEY ST.
 CONT: TBD/ TO BE DETERMINED
 CONTACT: KURT PFEFFER, P. E.
 TEL: (561)997-8070
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: MON. JULY06/ 2015
 ACTION: DENIED
  
 NOTE: SPECIFICATION BOOKS WILL NOT BE REVIEWED AS PART
 OF ANY PLAN REVIEW IF SUBMITED THEY GET STAMPED VOID.
  
 1) THE SUBMITTED PLANS FOR THE CENTRIFUGE DEWATERING
 BUILDING ARE MISSING PLANS ACCORDING TO THE INDEX.
 MISSING FROM THIS REVIEW ARE SHEETS:
 A-DEW-29
  
 PLEASE EITHER REMOVE THE INDEX SHEETS 0002-6-GEN.02
 THROUGH 0005-6-GEN.05 OR VOID THEM OUT THEY ARE OF NO
 USE TO THIS PROJECT THE WAY IT WAS SUBMITTED. THE PLANS
 DO NOT FOLLOW THE INDEX BEING BROUGHT IN BY BUILDING
 TYPES. 107.2.1.4 QUALITY OF BUILDING PLANS.
  
 2) SHEET 0241-S GEN-01 GENERAL STRUCTURAL NOTES, NOTE
 G-3 PLEASE NOTE CORRECT PALM BEACH COUNTY AMENDMENTS,
 THE CITY OF WEST PALM BEACH IS UNDER HOME RULE AND THE
 CITY HAS ITS OWN CHAPTER 1 AMENDMENTS. 2010 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION.
  
 3) THIS BUILDING WILL REQUIRE A THRESHOLD INSPECTOR,
 OVER 50 FEET IN HEIGHT.
 THRESHOLD BUILDING FL S. S. 553.71(7) ?THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 3A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 3B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE. CONTACT KEN CONRAD MANAGER OF THE SPECIAL
 INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER
 INFORMATION BEFORE THE PERMIT MAY BE ISSUED.
  
 3C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 3D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 3E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE
 SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD:
 [email protected]
  
 3F) NOTICE! NO ACTION REQUIRED FOR PLAN REVIEW. FOR
 DIGITAL PLANS, AFTER PERMIT ISSUANCE, PLEASE E-MAIL THE
 PERMIT LIBRARIAN OF THE PERMIT BEING ISSUED, THE PERMIT
 LIBRARIAN WILL THEN E-MAIL YOU THE APPROVED AND BATCH
 STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO SETS OF
 PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR THE
 THRESHOLD INSPECTOR, THE OTHER FOR THE MEP INSPECTORS
 OTHER PLANS YOU WISH TO PRINT MAYBE IN BLACK & WHITE..
  
 3G) NOTICE NO ACTION IS REQUIRED FOR PLAN REVIEW.
 PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 3H) NOTICE NO ACTION IS REQUIRED FOR PLAN REVIEW.
 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR
 THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER HAS
 REQUIRED ON THE PLANS OR SPECIFICATIONS ONE MATERIAL,
 APPROVED FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND
 CEILINGS.
  
 4) SHEET 0394-A-DEW-01:
 4A) CONSTRUCTION TYPE- TYPE I-B -UNPROTECTED, PLEASE
 NOTE TABLE 601 DOES REQUIRE 1,2, OR 3 HOUR FIRE
 PROTECTION OF STRUCTURAL MEMBERS ALSO SEE FOOTNOTES
  
 4B) CONSTRUCTION TYPE- TYPE I-B SPRINKLERED PER FBC-B
 602.2 - 602.2 HAS NOTHING TO DO WITH FIRE SPRINKLERS,
 IT DEALS WITH BUILDING ELEMENTS OF NON-COMBUSTIBLE
 MATERIALS AND ALLOWABLE USE OF FIRE-RETARDANT TREATED
 WOOD FRAMING.
  
 5) MISSING INFORMATION ENERGY FORMS 2010 FBC-ENERGY
 103.2 ENERGY REPORTING FORMS. INFORMATION ON
 CONSTRUCTION DOCUMENTS. 103.2.1 CODE DEMONSTRATION
 FORMS. SEE TABLE 103.2.1. PLANS ARE MISSING THE
 REQUIRED INSULATION BY THE 2010 FBC-ENERGY 502 BUILDING
 ENVELOPE REQUIREMENTS OR 506 TOTAL BUILDING
 PERFORMANCE.
  
 6) PLANS ARE MISSING 2010 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.41 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS & ROOF HATCH.
 (B) WINDOW
 (C), WALL LOUVERS, EFIS SYSTEMS
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) PRE-ENGINEERED A/C STANDS IF ROOF TOP
  
 7) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 8) SHEET 0312- S-DEW-06 PRESSURES FOR COMPONENTS AND
 CLADDING EXPOSURE "C" @ 180 MPH, 60 FT. ABOVE GRADE,
 ARE LOW FOR BOTH THE ROOF ZONES AND WALL ZONES.
 MULTIPLIER OF 1.62 FOR HEIGH FOR VULT PRESSURES. PLEASE
 ALSO SUPPLY PRESSURES IN VASD SINCE ALL PRODUCT
 APPROVALS ARE IN VASD.
  
 9) SHEET 365-A-GEN-02 WAS INCLUDED IN THIS PERMIT
 PACKAGE DOOR SCHEDULES BUT NOT FOR THE CENTRIFUGE
 DEWATERING BUILDING, NOT ON ANY OF THE BUILDING
 SCEDULES.
 107.3.5.1.1 (4 & 7) DOOR SCHEDULE- PROTECTION OF
 OPENINGS, MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL
 BUILDINGS.
  
 10) SHEET 0364-A-DEW-01 DOES NOT PROVIDE A WALL LEGEND
 INDICATING THE RATING OF THE INTERIOR WALLS.
 107.3.5.1.1 (4) MINIMUM PLAN REVIEW CRITERIA FOR
 COMMERCIAL BUILDINGS. FIRE-RESISTANT CONSTRUCTION
 REQUIREMENTS SHALL INCLUDE THE FOLLOWING COMPONENTS:
 FIRE RATING OF INTERIOR WALLS
  
 11) SHEET 0364-A-DEW-01. THE CODE SHEET SHOWS THE 3
 FLOORS OF THE BUILDING WITH VARIOUS WALLS IDENTIFIED AS
 RATED WALLS BUT THERE ARE NO WALL TAGS IDENTIFYING THE
 WALL TYPES FOR FIRE RESISTANCE RATING AND TYPE OF
 MATERIALS THEY WILL BE CONSTRUCTED. 107.3.5.1.1 (4)
 MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL BUILDINGS.
 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL
 INCLUDE THE FOLLOWING COMPONENTS: FIRE RATING OF
 INTERIOR WALLS,
  
 INTERIOR VERTICAL EXIT ENCLOSURE FBC-B 1022.1.
  
 ELEVATOR MACHINE ROOM FBC-B 3006.4
  
 THIRD FLOOR EXTERIOR WALL AT EXTERIOR STAIR FBC-B
 1026.6 PROTECTION OF EXTERIOR STAIR PROTECTION.
  
 12) ) PROVIDE CODE COMPLIANCE WITH: 2010 FBC-B 713.6
 FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE
 BARRIERS AND SMOKE PARTITIONS OR ANY OTHER WALL
 REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE
 EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY
 HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE
 ANY DECORATIVE CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: ?FIRE
 AND SMOKE BARRIER ? PROTECT ALL OPENINGS.?
  
  
 13) SHEET 0410-A-DEW- 17 SHOWS FLOOR OPENINGS ON THE
 2ND & 3RD FLOOR THAT ALLOW THE 3 FLOORS TO COMMUNICATE
 WITHOUT AND WITHOUT A SHAFT ENCLOSURE, PLEASE SHOW
 COMPLIANCE WITH 2010FBC-B 708.2 OR AN EXCEPTION.
  
 1) SHEET 0419-A-DEW-26. DETAIL # 1 1ST FLOOR ACCESSIBLE
 BATHROOM.
 14A) PLEASE PROVIDE THE DIMENSION FROM THE CENTERLINE
 OF THE WATERCLOSET TO THE FINISH OF THE CLOSEST
 INTERIOR WALL NOT THE CENTERLINE OF THE WALL, SHOW
 COMPLIANCE WITH 2010 FBC-ACCESIBLITY CODE 604.2
  
 14B) PLEASE PROVIDE DIMENSIONS SHOWING COMPLIANCE WITH
 2010 FBC-ACCESSIBLITY CODE FIGURE 604.3.1.
  
 14C) SHEET 0394-A-DEW-01 ONLY SHOWS AN ACCESSIBLE
 BATHROOM ON THE 1ST FLOOR. NEITHER THE 2ND FLOOR OR 3RD
 FLOOR INDICACATE COMPLIANCE WITH THE 2010 FL PLUMBING
 CODE DOES ALLOW TRAVEL DISTANCE OF ONE FLOOR TO REACH A
 RESTROOM AND OR BATHROOMS. 2010 FL ACCESS. 213.2
 TOILET.
  
 15) SHEET 0396- A-DEW- 03/05 OR 06 DO NOT PROVIDE A
 DRINKING AN ACCESSIBLE DRINKING FOUNTAIN. 2010
 FBC-ACCESS. 211.2 MINIMUM NUMBER.NO FEWER THAN TWO
 DRINKING FOUNTAINS SHALL BE PROVIDED. ONE DRINKING
 FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH 602.6 AND ONE
 DRINKING FOUNTAIN SHALL COMPLY WITH 602.7.
  
 16) SHEET 0409-A-DEW-16. NOTES THAT THE PRE-FABRICATED
 METAL CANOPY WILL BE DESIGNED BY A DELEGATE ENGINEER.
 PLEASE PROVIDE THE WIND DESIGN CRITERIA THAT THE CANOPY
 HAS TO BE DESIGNED TO. ASCE 7-10/ FBC-B 3105.5.1 LOADS.
  
 17) SHEET 0409-A-DEW-16. SHOWS A EXTERIOR STAIR,
 GUARDRAI / HANDRAIL SYSTEM THERE IS A NOTE INDICATING
 SEE 4/ A-DEW-29, THIS IS A MISSING SHEET. NO PLAN
 REVIEW OF THE EXTERIOR STAIR CAN BE COMPLETED.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 18) SHEET 0409-A-DEW-16 SHOWS WINDOWS, DOORS AND WALL
 LOUVERS WITHIN 10 FT. OF THE STAIRS AND LANDINGS.
 PLEASE PROVIDE CODE COMPLIANCE WITH 1026.6. EXTERIOR
 STAIR PROTECTION.
  
 19) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676