Plan Review Notes
Plan Review Notes For Permit 15060562
Permit Number 15060562
Review Stop P
Sequence Number 3
Notes
Date Text
2015-11-09 05:53:54PROVISO
  
 1) SHT.0371-A-MEB-03 - THE ROOF DRAIN CALCULATION TABLE
 CALLS OUT 8" X 8" SCUPPERS AND OVERFLOW SCUPPERS BUT
 SHT. 0386-A-ADF-08 - DETAILS 0750009, 0763009 & 0763010
 SHOW THE SCUPPERS AS 4" X 8". CLARIFY.
 2) ) SHT.0369 - A-MEB-01 STATES THAT RESTROOMS ARE
 WITHIN 500 FEET OF THIS STRUCTURE AND REFER TO SHT. C -
 GEN - 01 FOR LOCATION OF SAID RESTROOMS. SHT. C -
 GEN-01 DOES NOT IDENTIFY WHICH ADJACENT BUILDING THE
 RESTROOMS ARE LOCATED AND DOES NOT STATE THAT THE
 RESTROOMS ARE WITHIN THE 500 FEET PARAMETERS. WPB
 AMEND. TO FBC SEC. 107.2.1, 2010 FBC-PLUMBING
 SEC.403.3.2. 3RD REQUEST.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  