2015-10-24 06:20:591) SHT.0369 - A-MEB-01 STATES THAT RESTROOMS ARE WITHIN
 500 FEET OF THIS STRUCTURE AND REFER TO SHT. 0013 - C -
 GEN - 01 FOR LOCATION OF SAID RESTROOMS. SHT.0013 - C -
 GEN DOES NOT IDENTIFY WHICH ADJACENT BUILDING THE
 RESTROOMS ARE LOCATED AND DOES NOT STATE THAT THE
 RESTRROMS ARE WITHIN THE 500 FEET PARAMETERS. WPB
 AMEND. TO FBC SEC. 107.2.1.
 2) SHT. 0371- A - MEB - 03 APPEARS TO SHOW THE PRIMARY
 SCUPPERS LOCATED IN THE COLUMNS AND THE RESPONSE
 NARRATIVE FROM THE DESIGN TEAM REFERS TO DETAIL
 A/SHT.0373 - A - MEB - 05 FOR THE WALL SECTION SHOWING
 THE SCUPPERS IN THE PARAPET. SHT. 0373 -A - MEB - 05 IS
 NOT INCLUDED IN THIS SET OF PLANS.PLEASE INCLUDE THIS
 SHEET FOR REVIEW .WPB AMEND. TO FBC SEC. 107.2.1.
 3) SHT. 0371- A - MEB - 03 - FBC 2010 SEC.1503.4.2.1
 OVERFLOW SCUPPERS - OVERFLOW SCUPPERS SHALL BE LOCATED
 NO LESS THAN 2 INCHES NOR MORE THAN 4 INCHES ABOVE THE
 FINISHED ROOF COVERING AND SHALL BE LOCATED AS CLOSE AS
 PRACTICAL TO REQUIRED VERTICAL LEADERS OR DOWNSPOUTS OR
 WALL AND PARAPET SCUPPERS. NOTE # 2 STATES THE OVERFLOW
 SCUPPER WILL BE 3 INCHES ABOVE THE PRIMARY SCUPPER.
 INCLUDE IN THE NOTE THAT THE OVERFLOW SCUPPER SHALL BE
 NO LESS THAN 2 INCHES NOR MORE THAN 4 INCHES ABOVE THE
 FINISHED ROOF SURFACE.THIS IS THE LANGUAGE IN THE CODE.
 NOTE #2 STATES "3 INCHES ABOVE THE PRIMARY SCUPPER".
 THIS COULD POSSIBLY BE MISINTERPRETED AS MEANING THE
 TOP OF THE SCUPPER.
  