| 2015-10-22 12:09:18 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15060562 MAIN ELECTRIC BUILDING |
| | ADD: 4395 EASLEY ST. |
| | CONT: TBD/ TO BE DETERMINED |
| | CONTACT: KURT PFEFFER, P. E. |
| | TEL: (561)997-8070 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2ND REVIEW |
| | DATE: THURS. OCT. 22 2015 |
| | ACTION: DENIED |
| | |
| | 1-5) COMPLIED> |
| | |
| | |
| | |
| | |
| | |
| | 6) 2ND REQUEST. RESPONSE INDICATES WIND DESIGN CRITERIA |
| | IS FOUND ON SHEET 0241-S-GEN-01. FOR THE MAIN ELECTRIC |
| | BUILDING THE PRESSURE COEFFICIENT IS LABELED AS +/- |
| | 0.55 OR PARTIALLY ENCLOSED. PLEASE NOTE THE ROOF AND |
| | WALL PRESSURES CAN NOT BE VEERIFIED AS A PARTIALLY OPEN |
| | BUILDING. THE INDEX LIST SHEET 0372 AS THE ELEVATION |
| | SHEET, THIS SHEET IS NOT INCLUDED IN THE PLAN SET OF |
| | DRAWING SUBMITTED. |
| | COMMENTS 6A-6D CAN NOT BE VERIFIED. |
| | |
| | 6E) NEW COMMENT, ALSO MISSING SHEET 0373-A-MEB-05 WALL |
| | SECTIONS. |
| | |
| | 1ST REVIEW COMMENT. PAGE 0244-S-MEB-02: |
| | 6A) NOTES PRECAST PRESTRESSED ELEMENTS SHALL BE |
| | DESIGNED FOR THE FOLLOWING: |
| | 1( E ) WIND LOADS PER CODE. ? NOT GIVEN. PROVIDE THE |
| | DESIGN CRITERIA, 0244-SHEET S-MEB-02 PRESSURES FOR |
| | COMPONENTS AND CLADDING EXPOSURE "C" @ 180 MPH, 38 FT |
| | ABOVE GRADE, VASD FOR ROOF ZONE 2 ARE LOW, WE TAKE THE |
| | PRESSURES AT 10 SQ. FT. FOR ROOF TOP FASTENERS, ASSUMED |
| | VASD. 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 2010 |
| | FBC-B 1609.6.4.41 COMPONENTS & CLADDING |
| | |
| | 6B) NOTE 1( F ) EQUIPMENT LOADS. NOT GIVEN . |
| | |
| | 6C) ROOF PRESSURES SUBMITTED DO NOT STATE IF THEY ARE |
| | VULT OR VASD. PRESSURES ARE LOW CONSIDERING THE WIND |
| | DESIGN CRITERIA OF DESIGN CRITERIA, 180 VULT, EXPOSURE |
| | C, MEAN ROOF HEIGHT 38 FT. BUILD RISK CAT. III. |
| | |
| | 6D) SHEET 0244-S-MEB-02 NOR -03 PRESSURES FOR THE DOOR |
| | OPENINGS ARE NOT PROVIDED FOR THIS BUILDING. 2010 FBC-B |
| | 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 |
| | COMPONENTS & CLADDING. |
| | |
| | |
| | 7) DEFERRED SUBMITTAL: 107.3.4.2 DEFERRED SUBMITTALS. |
| | FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS |
| | ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE |
| | NOT SUBMITTED AT THE TIME OF THE |
| | APPLICATION AND THAT ARE TO BE SUBMITTED TO THE |
| | BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL |
| | OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF |
| | THE BUILDING OFFICIAL. THE REGISTERED DESIGN |
| | PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE |
| | DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR |
| | REVIEW BY THE BUILDING OFFICIAL. |
| | |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) WALL LOUVERS |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | |
| | 8) DEFERRED SUBMITTAL. 2010 FBC 107.3.4.1 PRODUCT |
| | APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE |
| | DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | 9) SHEET 0370- A-MEB-02 SHOWS WALL IDENTIFICATION TAGS |
| | AND DOOR AND WINDOW IDENTIFICATION TAGS THE MAIN |
| | ELECTRIC BUILDING PLANS DO NOT HAVE SCHEDULES LISTED |
| | WITHIN THE 5 SHEETS OF THE ARCHITECTURAL SHEETS. |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. T |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL INCLUDE |
| | THE FOLLOWING COMPONENTS: |
| | FIRE-RESISTANT SEPARATIONS WALLS, DOORS & WINDOWS |
| | |
| | 10) 2ND REQUEST. RESPONSE INDICATES THE COLUMNS STOP |
| | BELOW THE ROOF STRUCTURE IN WALL SECTIONA/A-MEB-05. |
| | PLEASE NOTE THE INDEX INDICATES THERE SHOULD BE A |
| | 0372-A-MEB-04 AND 0373-A-MEB-05. IN THE ACTUAL PLAN SET |
| | THE INDEX NUMBER 0371-S-MEB-03 JUMPS TO 0478-E-GEN-01, |
| | PLEASE UPLOAD THE MISSING SHEETS. |
| | |
| | 1ST ROUND OF COMMENTS. SHEET 0371- A-MEB-03 SHOWS THE |
| | LOCATION OF THE SCUPPERS BUT IT DOES NOT SHOW THEY ARE |
| | DIRECTLY IN FRONT OF THE 16X16 INCH COLUMN AND HOW IS |
| | THE STEEL RE-INFORCEMENT AND THE SCUPPER GOING TO FIT |
| | INTO THE SAME COLUMN. SEE 2010 FBC-B 1906.3 CONDUITS |
| | AND PIPES EMBEDDED IN CONCRETE. |
| | CONDUITS, PIPES AND SLEEVES OF ANY MATERIAL NOT HARMFUL |
| | TO CONCRETE AND WITHIN THE LIMITATIONS OF ACI 318, |
| | SECTION 6.3, ARE PERMITTED TO BE EMBEDDED IN CONCRETE |
| | WITH APPROVAL OF THE REGISTERED DESIGN PROFESSIONAL. |
| | |
| | 11) COMPLIED. |
| | |
| | 12) . A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |