2015-10-22 12:09:18BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15060562 MAIN ELECTRIC BUILDING
 ADD: 4395 EASLEY ST.
 CONT: TBD/ TO BE DETERMINED
 CONTACT: KURT PFEFFER, P. E.
 TEL: (561)997-8070
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2ND REVIEW
 DATE: THURS. OCT. 22 2015
 ACTION: DENIED
  
 1-5) COMPLIED>
  
  
  
  
  
 6) 2ND REQUEST. RESPONSE INDICATES WIND DESIGN CRITERIA
 IS FOUND ON SHEET 0241-S-GEN-01. FOR THE MAIN ELECTRIC
 BUILDING THE PRESSURE COEFFICIENT IS LABELED AS +/-
 0.55 OR PARTIALLY ENCLOSED. PLEASE NOTE THE ROOF AND
 WALL PRESSURES CAN NOT BE VEERIFIED AS A PARTIALLY OPEN
 BUILDING. THE INDEX LIST SHEET 0372 AS THE ELEVATION
 SHEET, THIS SHEET IS NOT INCLUDED IN THE PLAN SET OF
 DRAWING SUBMITTED.
 COMMENTS 6A-6D CAN NOT BE VERIFIED.
  
 6E) NEW COMMENT, ALSO MISSING SHEET 0373-A-MEB-05 WALL
 SECTIONS.
  
 1ST REVIEW COMMENT. PAGE 0244-S-MEB-02:
 6A) NOTES PRECAST PRESTRESSED ELEMENTS SHALL BE
 DESIGNED FOR THE FOLLOWING:
 1( E ) WIND LOADS PER CODE. ? NOT GIVEN. PROVIDE THE
 DESIGN CRITERIA, 0244-SHEET S-MEB-02 PRESSURES FOR
 COMPONENTS AND CLADDING EXPOSURE "C" @ 180 MPH, 38 FT
 ABOVE GRADE, VASD FOR ROOF ZONE 2 ARE LOW, WE TAKE THE
 PRESSURES AT 10 SQ. FT. FOR ROOF TOP FASTENERS, ASSUMED
 VASD. 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 2010
 FBC-B 1609.6.4.41 COMPONENTS & CLADDING
  
 6B) NOTE 1( F ) EQUIPMENT LOADS. NOT GIVEN .
  
 6C) ROOF PRESSURES SUBMITTED DO NOT STATE IF THEY ARE
 VULT OR VASD. PRESSURES ARE LOW CONSIDERING THE WIND
 DESIGN CRITERIA OF DESIGN CRITERIA, 180 VULT, EXPOSURE
 C, MEAN ROOF HEIGHT 38 FT. BUILD RISK CAT. III.
  
 6D) SHEET 0244-S-MEB-02 NOR -03 PRESSURES FOR THE DOOR
 OPENINGS ARE NOT PROVIDED FOR THIS BUILDING. 2010 FBC-B
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING.
  
  
 7) DEFERRED SUBMITTAL: 107.3.4.2 DEFERRED SUBMITTALS.
 FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS
 ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE
 NOT SUBMITTED AT THE TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL
 OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF
 THE BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR
 REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) WALL LOUVERS
 (D) ROOFING PRODUCTS AND ASSEMBLIES
  
 8) DEFERRED SUBMITTAL. 2010 FBC 107.3.4.1 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 9) SHEET 0370- A-MEB-02 SHOWS WALL IDENTIFICATION TAGS
 AND DOOR AND WINDOW IDENTIFICATION TAGS THE MAIN
 ELECTRIC BUILDING PLANS DO NOT HAVE SCHEDULES LISTED
 WITHIN THE 5 SHEETS OF THE ARCHITECTURAL SHEETS.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. T
 107.3.5.1 COMMERCIAL BUILDINGS:
 FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL INCLUDE
 THE FOLLOWING COMPONENTS:
 FIRE-RESISTANT SEPARATIONS WALLS, DOORS & WINDOWS
  
 10) 2ND REQUEST. RESPONSE INDICATES THE COLUMNS STOP
 BELOW THE ROOF STRUCTURE IN WALL SECTIONA/A-MEB-05.
 PLEASE NOTE THE INDEX INDICATES THERE SHOULD BE A
 0372-A-MEB-04 AND 0373-A-MEB-05. IN THE ACTUAL PLAN SET
 THE INDEX NUMBER 0371-S-MEB-03 JUMPS TO 0478-E-GEN-01,
 PLEASE UPLOAD THE MISSING SHEETS.
  
 1ST ROUND OF COMMENTS. SHEET 0371- A-MEB-03 SHOWS THE
 LOCATION OF THE SCUPPERS BUT IT DOES NOT SHOW THEY ARE
 DIRECTLY IN FRONT OF THE 16X16 INCH COLUMN AND HOW IS
 THE STEEL RE-INFORCEMENT AND THE SCUPPER GOING TO FIT
 INTO THE SAME COLUMN. SEE 2010 FBC-B 1906.3 CONDUITS
 AND PIPES EMBEDDED IN CONCRETE.
 CONDUITS, PIPES AND SLEEVES OF ANY MATERIAL NOT HARMFUL
 TO CONCRETE AND WITHIN THE LIMITATIONS OF ACI 318,
 SECTION 6.3, ARE PERMITTED TO BE EMBEDDED IN CONCRETE
 WITH APPROVAL OF THE REGISTERED DESIGN PROFESSIONAL.
  
 11) COMPLIED.
  
 12) . A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  