Plan Review Notes
Plan Review Notes For Permit 15060562
Permit Number 15060562
Review Stop P
Sequence Number 1
Notes
Date Text
2015-07-22 06:32:201) THE SCUPPERS SHALL BE SIZED IN ACCORDANCE WITH TABLE
 1106.7, NOT 1106.1 AS SHOWN. SHOW THAT THE CALCULATIONS
 INCLUDE 1/2 THE AREA OF ANY VERTICAL WALL THAT DIVERTS
 RAINWATER TO THE ROOF PER 2010 FBC-PLUMBING SEC.
 1106.4.
 2) SHT. A-MEB-01 STATES THAT RESTROOMS ARE WITHIN 500
 FEET OF THIS STRUCTURE AND REFER TO SHT. C-GEN-01.
 SUBMIT THIS SHEET FOR REVIEW WITH THIS SET OF PLANS.
 WPB AMEND. TO FBC SEC. 107.2.1.
 3) SHT. A-MEB-03 SHOWS THE PRIMARY SCUPPERS LOCATED IN
 THE COLUMNS.PIPES, CONDUIT AND SLEEVES EMBEDDED IN
 CONCRETE SHALL COMPLY WITH 2010 FBC-BUILDING,
 SEC.1906.3.
 4) FBC 2010 SEC.1503.4.2.1 OVERFLOW SCUPPERS.
 WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS NOT
 PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN WALLS OR
 PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR MORE THAN 4
 INCHES (102 MM) ABOVE THE FINISHED ROOF COVERING AND
 SHALL BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED
 VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND PARAPET
 SCUPPERS. AN OVERFLOW SCUPPER SHALL BE SIZED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING.
 5) THE SIZING OF THE ROOF SCUPPERS SHALL BE BASED ON A
 RAINFALL RATE OF 5 INCHES. THERE IS NO 4.5 INCH
 RAINFALL RATE SO IT MUST BE ROUNDED UP TO 5 INCHES.
 6) SHT. H-STD-01 - DETAIL 01 - SHOW THE SIZE OF THE
 CONDENSATE DRAIN.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  