| Plan Review Notes For Permit 15060561 |
| Permit Number |
15060561 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-03-31 11:10:01 | 2ND REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15060561 | | | 3/31/16 | | | | | | 1) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE | | | OFFICE AND STORAGE ROOMS PER TABLE 403.3 FBC-10 | | | MECHANICAL, AND INDICATE HOW THE O/A SUPPLY WILL BE | | | CONTROLLED IN ACCORDANCE WITH SECTION 503.2.5.4 FBC-10 | | | ENERGY CONSERVATION. | | | 2) PROVIDE A DS (DUCT SMOKE DETECTOR) SYMBOL IN THE | | | MAIN SUPPLY PLENUM OF AC-2 | | | 3) PROVIDE WIND-LOAD TIE DOWN ENGINEERING FOR FOR THE | | | ROOFTOP AC-2, EF-1, AND THE GROUND-MOUNTED ACCU-1: SEE | | | SECTION 301.12 FBC-10 MECHANICAL. | | | 4) PROVIDE AN INSTALLATION DETAIL FOR THE | | | CEILING-MOUNTED AC-1 UNIT IN THE ELECTRICAL ROOM | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|