2016-03-31 11:10:012ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #15060561
 3/31/16
  
 1) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE
 OFFICE AND STORAGE ROOMS PER TABLE 403.3 FBC-10
 MECHANICAL, AND INDICATE HOW THE O/A SUPPLY WILL BE
 CONTROLLED IN ACCORDANCE WITH SECTION 503.2.5.4 FBC-10
 ENERGY CONSERVATION.
 2) PROVIDE A DS (DUCT SMOKE DETECTOR) SYMBOL IN THE
 MAIN SUPPLY PLENUM OF AC-2
 3) PROVIDE WIND-LOAD TIE DOWN ENGINEERING FOR FOR THE
 ROOFTOP AC-2, EF-1, AND THE GROUND-MOUNTED ACCU-1: SEE
 SECTION 301.12 FBC-10 MECHANICAL.
 4) PROVIDE AN INSTALLATION DETAIL FOR THE
 CEILING-MOUNTED AC-1 UNIT IN THE ELECTRICAL ROOM
  