| 2015-07-27 06:22:28 | 1) SUBMIT A SCUPPER & OVERFLOW SCUPPER DETAIL WITH | | | THESE PLANS. THE SCUPPER SHALL BE INSTALLED AND LOCATED | | | IN ACCORDANCE WITH 2010 FBC SEC.1503.4.2 AND THE | | | OVERFLOW SHALL BE INSTALLED AND LOCATED PER | | | SEC.1503.4.2.1. SHT.0424-A-FOG-2 NOTE # 2 INDICATES THE | | | OVERFLOW SCUPPER TO BE LOCATED 3" ABOVE PRIMARY | | | SCUPPER. | | | 2) THE DRAINAGE CALCULATIONS FOR THE SIZING OF THE | | | SCUPPERRS SHALL INCLUDE 1/2 THE AREA OF ANY VERTICAL | | | WALL THAT DIVERTS RAINWATER TO THE ROOF PER 2010 FPC | | | SEC.1106.4. INDICATE THIS SQUARE FOOTAGE IN THE ROOF | | | DRAINAGE CALCULATION. | | | 3) SCUPPERS SHALL BE SIZED IN ACCORDANCE WITH TABLE | | | 1106.7. | | | 4) SUBMIT A SANITARY AND WATER RISER FOR REVIEW. WPB | | | AMEND. TO 2010 FBC SEC. 107.3.5.1.3. | | | 5) SUBMIT ALL DRAWINGS APPLICABLE FOR THIS PORTION OF | | | THE PROJECT. WPB AMEND. TO 2010 FBC SEC. 107.2.1. | | | 6) INDICATE THE HEIGHT OF THE SCUPPER HEAD DESIGN PER | | | TABLE 1106.7 OF 2010 FPC. | | | | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|