| 2015-08-05 07:42:37 | 1ST REVIEW: FBC 2010 MECHANICAL | | | PERMIT #15060561 SFOG ATTENDANT BUILDING | | | 8/5/15 | | | | | | 1) THE HVAC PLANS FOR THE BUILDING WERE NOT UPLOADED | | | FOR REVIEW: PLEASE PROVIDE THE PLANS. | | | 2) SHEET M-STD-03 (INCLUSIVE OF ALL PERMIT PLAN SETS | | | CONTAINING THIS SHEET): REVISE NOTES #10 & 13 | | | REFERENCING THE CITY OF TALLAHASSEE FIRE HYDRANT | | | COMPLIANCE INFORMATION. | | | 3) BASED ON THE SOILS REPORT- PIPE BEDDING AND | | | DEWATERING GUIDELINES, PLEASE PROVIDE PIPE TRENCH | | | CROSS-SECTION DETAILS FOR TYPICAL INSTALLATIONS AND | | | HIGH WATER TABLE INSTALLATIONS. INDICATE TRENCH | | | DIMENSIONS, PIPE EMBEDMENT DEPTHS, BEDDING MATERIALS | | | AND THICKNESSES, COMPACTION AND BACKFILLING | | | SPECIFICATIONS. | | | 4) PROVIDE CIVIL DRAWINGS THAT INCLUDE OVERALL | | | UNDERGROUND PIPING LAYOUTS, AND ENLARGED AREA DRAWINGS | | | DEPICTING THE UNDERGROUND PIPINGS SPECIFICALLY | | | SERVICING EACH TANK, FACILITY, BUILDING, ETC. | | | 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR PIPINGS AND | | | FITTINGS REVIEWED AND APPROVED BY THE DESIGN | | | PROFESSIONAL OF RECORD. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|