| Date |
Text |
| 2015-06-23 16:06:20 | 4395 EASLEY DRIVE - SFOG ATTENDANT BUILDING |
| | PERMIT #15060561 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | UPDATE THE CODE LIST TO REFERENCE THE 5TH EDITION OF |
| | THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE |
| | 2012 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA |
| | AMENDMENTS. |
| | |
| | GENERAL: PER NFPA 101 SECTION 8.3.2.4, EACH FIRE |
| | BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH SIGNS OR |
| | STENCILING READING FIRE BARRIER-PROTECT ALL OPENINGS. |
| | CHARACTERS SHALL BE AT LEAST 4-INCHES IN HEIGHT AND |
| | HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE SPACED NOT |
| | MORE THAN 15 FEET ON CENTER. |
| | |
| | GENERAL: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT |
| | DOORS WITH EXIT SIGNS. |
| | |
| | GENERAL: PER SECTION 10.12.1.2 (NFPA 1), PROVIDE |
| | BUILDING ADDRESSES OR NAMES THAT ARE VISIBLE FROM THE |
| | STREET. NUMBERS/LETTERS SHALL BE ATTACHED TO THE |
| | BUILDING AND BE AT LEAST SIX-INCHES IN HEIGHT WITH |
| | 1-INCH STROKE AND SHALL CONTRAST THE BACKGROUND. |
| | |
| | ELECTRICAL ROOMS: PER NFPA 70 ARTICLE 110.26(C)(3) |
| | PERSONNEL DOORS. WHERE CONDUCTORS AND EQUIPMENT USED ON |
| | CIRCUITS ARE OVER 600 VOLTS OR EQUIPMENT IS RATED 1200 |
| | A OR MORE THAT CONTAINS OVERCURRENT DEVICES, SWITCHING |
| | DEVICES, OR CONTROL DEVICES IS INSTALLED AND THERE IS A |
| | PERSONNEL DOOR(S) INTENDED FOR ENTRANCE TO AND EGRESS |
| | FROM THE WORKING SPACE LESS THAN 25 FEET FROM THE |
| | NEAREST EDGE OF THE WORKING SPACE, THE DOOR(S) SHALL |
| | OPEN IN THE DIRECTION OF EGRESS AND BE EQUIPPED WITH |
| | PANIC BARS, PRESSURE PLATES, OR OTHER DEVICES THAT ARE |
| | NORMALLY LATCHED BUT OPEN UNDER SIMPLE PRESSURE. |
| | CONFIRM CIRCUITS ARE NOT OVER 600 VOLTS AND EQUIPMENT |
| | IS NOT RATED 1200 A OR MORE. |
| | |
| | WESLEY JOLIN |
| | ASSISTANT FIRE MARSHAL |
| | FIRE INVESTIGATOR & INSPECTOR |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | (561) 805-6730 |