Plan Review Notes
Plan Review Notes For Permit 15060561
Permit Number 15060561
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2015-06-23 16:06:204395 EASLEY DRIVE - SFOG ATTENDANT BUILDING
 PERMIT #15060561
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 UPDATE THE CODE LIST TO REFERENCE THE 5TH EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2012 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 GENERAL: PER NFPA 101 SECTION 8.3.2.4, EACH FIRE
 BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH SIGNS OR
 STENCILING READING FIRE BARRIER-PROTECT ALL OPENINGS.
 CHARACTERS SHALL BE AT LEAST 4-INCHES IN HEIGHT AND
 HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE SPACED NOT
 MORE THAN 15 FEET ON CENTER.
  
 GENERAL: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT
 DOORS WITH EXIT SIGNS.
  
 GENERAL: PER SECTION 10.12.1.2 (NFPA 1), PROVIDE
 BUILDING ADDRESSES OR NAMES THAT ARE VISIBLE FROM THE
 STREET. NUMBERS/LETTERS SHALL BE ATTACHED TO THE
 BUILDING AND BE AT LEAST SIX-INCHES IN HEIGHT WITH
 1-INCH STROKE AND SHALL CONTRAST THE BACKGROUND.
  
 ELECTRICAL ROOMS: PER NFPA 70 ARTICLE 110.26(C)(3)
 PERSONNEL DOORS. WHERE CONDUCTORS AND EQUIPMENT USED ON
 CIRCUITS ARE OVER 600 VOLTS OR EQUIPMENT IS RATED 1200
 A OR MORE THAT CONTAINS OVERCURRENT DEVICES, SWITCHING
 DEVICES, OR CONTROL DEVICES IS INSTALLED AND THERE IS A
 PERSONNEL DOOR(S) INTENDED FOR ENTRANCE TO AND EGRESS
 FROM THE WORKING SPACE LESS THAN 25 FEET FROM THE
 NEAREST EDGE OF THE WORKING SPACE, THE DOOR(S) SHALL
 OPEN IN THE DIRECTION OF EGRESS AND BE EQUIPPED WITH
 PANIC BARS, PRESSURE PLATES, OR OTHER DEVICES THAT ARE
 NORMALLY LATCHED BUT OPEN UNDER SIMPLE PRESSURE.
 CONFIRM CIRCUITS ARE NOT OVER 600 VOLTS AND EQUIPMENT
 IS NOT RATED 1200 A OR MORE.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved