2015-07-27 15:56:521ST REVIEW: FBC 2010 MECHANICAL
 PERMIT #15060559
 7/27/15
  
 1) SHEET M-STD-03 (INCLUSIVE OF ALL PERMIT PLAN SETS
 CONTAINING THIS SHEET): REVISE NOTES #10 & 13
 REFERENCING THE CITY OF TALLAHASSEE FIRE HYDRANT
 COMPLIANCE INFORMATION.
 2) BASED ON THE SOILS REPORT- PIPE BEDDING AND
 DEWATERING GUIDELINES, PLEASE PROVIDE PIPE TRENCH
 CROSS-SECTION DETAILS FOR TYPICAL INSTALLATIONS AND
 HIGH WATER TABLE INSTALLATIONS. INDICATE TRENCH
 DIMENSIONS, PIPE EMBEDMENT DEPTHS, BEDDING MATERIALS
 AND THICKNESSES, COMPACTION AND BACKFILLING
 SPECIFICATIONS.
 3) PROVIDE CIVIL DRAWINGS THAT INCLUDE OVERALL
 UNDERGROUND PIPING LAYOUTS, AND ENLARGED AREA DRAWINGS
 DEPICTING THE UNDERGROUND PIPINGS SPECIFICALLY
 SERVICING EACH TANK, FACILITY, BUILDING, ETC.
 4) PROVIDE DIMENSIONED SECTION VIEWS AND DETAILS FOR
 INSTALLATION OF THE ALUMINUM GUARDRAILS ON THE
 PLATFORMS- REFER TO SECTIONS 304.11 FBC-10 MECHANICAL.
 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FA
 DUCTS REVIEWED AND APPROVED BY THE DESIGN PROFESSIONAL
 OF RECORD.
 6) PROVIDE WIND LOAD DESIGN CRITERIA, AND ENGINEERED
 DETAILS FOR ANCHORING ALL THE EQUIPMENT AND SYSTEMS
 EXPOSED TO WIND- SECTION 301.12 FBC-10 MECHANICAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  