Plan Review Notes
Plan Review Notes For Permit 15060558
Permit Number 15060558
Review Stop M
Sequence Number 1
Notes
Date Text
2015-08-04 08:15:241ST REVIEW: FBC 2010 MECHANICAL
 PERMIT #15060558 FERRIC CHLORIDE FACILITY
 8/4/15
  
 1) SUBMIT MSDS SHEETS FOR THE FERRIC CHLORIDE
 2) REFER TO SECTIONS 414.3 FBC-10 BUILDING AND 502.9
 FBC-10 MECHANICAL, AND PROVIDE AN EXHAUST VENTILATION
 PLAN FOR THE STORAGE FACILITY.
 PROVIDE ON THE PLAN: A) VENTILATION CALCULATIONS B) THE
 SOURCE OF MAKEUP AIR. C) THE LOCATION OF THE EXHAUST
 FAN(S). D) FAN EQUIPMENT SCHEDULES E) SEQUENCE OF
 OPERATION DIAGRAM AND NARRATIVE DECRIPTION- REFER TO
 SECTION 502.8.1.1 FBC-10 MECHANICAL- SYSTEMS
 REQUIREMENTS:
 EXHAUST VENTILATION SYSTEMS SHALL COMPLY WITH ALL OF
 THE FOLLOWING:
 1. THE INSTALLATION SHALL BE IN ACCORDANCE WITH THIS
 CODE.
 2. MECHANICAL VENTILATION SHALL BE PROVIDED AT A RATE
 OF NOT LESS THAN 1 CFM PER SQUARE FOOT [0.00508 M3/(S ?
 M2)] OF FLOOR AREA OVER THE STORAGE AREA.
 3. THE SYSTEMS SHALL OPERATE CONTINUOUSLY UNLESS
 ALTERNATE DESIGNS ARE APPROVED.
 4. A MANUAL SHUTOFF CONTROL SHALL BE PROVIDED OUTSIDE
 OF THE ROOM IN A POSITION ADJACENT TO THE ACCESS DOOR
 TO THE ROOM OR IN ANOTHER APPROVED LOCATION. THE SWITCH
 SHALL BE A BREAK-GLASS OR OTHER APPROVED TYPE AND SHALL
 BE LABELED: VENTILATION SYSTEM EMERGENCY SHUTOFF.
 5. THE EXHAUST VENTILATION SHALL BE DESIGNED TO
 CONSIDER THE DENSITY OF THE POTENTIAL FUMES OR VAPORS
 RELEASED. FOR FUMES OR VAPORS THAT ARE HEAVIER THAN
 AIR, EXHAUST SHALL BE TAKEN FROM A POINT WITHIN 12
 INCHES (305 MM) OF THE FLOOR. FOR FUMES OR VAPORS THAT
 ARE LIGHTER THAN AIR, EXHAUST SHALL BE TAKEN FROM A
 POINT WITHIN 12 INCHES (305 MM) OF THE HIGHEST POINT OF
 THE ROOM.
 6. THE LOCATION OF BOTH THE EXHAUST AND INLET AIR
 OPENINGS SHALL BE DESIGNED TO PROVIDE AIR MOVEMENT
 ACROSS ALL PORTIONS OF THE FLOOR OR ROOM TO PREVENT THE
 ACCUMULATION OF VAPORS.
 7. THE EXHAUST AIR SHALL NOT BE RECIRCULATED TO
 OCCUPIED AREAS IF THE MATERIALS STORED ARE CAPABLE OF
 EMITTING HAZARDOUS VAPORS AND CONTAMINANTS HAVE NOT
 BEEN REMOVED. AIR CONTAMINATED WITH EXPLOSIVE OR
 FLAMMABLE VAPORS, FUMES OR DUSTS; FLAMMABLE, HIGHLY
 TOXIC OR TOXIC GASES; OR RADIOACTIVE MATERIALS SHALL
 NOT BE RECIRCULATED.
 8) SHEET M-STD-03 (INCLUSIVE OF ALL PERMIT PLAN SETS
 CONTAINING THIS SHEET): REVISE NOTES #10 & 13
 REFERENCING THE CITY OF TALLAHASSEE FIRE HYDRANT
 COMPLIANCE INFORMATION.
 9) BASED ON THE SOILS REPORT- PIPE BEDDING AND
 DEWATERING GUIDELINES, PLEASE PROVIDE PIPE TRENCH
 CROSS-SECTION DETAILS FOR TYPICAL INSTALLATIONS AND
 HIGH WATER TABLE INSTALLATIONS. INDICATE TRENCH
 DIMENSIONS, PIPE EMBEDMENT DEPTHS, BEDDING MATERIALS
 AND THICKNESSES, COMPACTION AND BACKFILLING
 SPECIFICATIONS.
 10) PROVIDE CIVIL DRAWINGS THAT INCLUDE OVERALL
 UNDERGROUND PIPING LAYOUTS, AND ENLARGED AREA DRAWINGS
 DEPICTING THE UNDERGROUND PIPINGS SPECIFICALLY
 SERVICING EACH TANK, FACILITY, BUILDING, ETC.
 11) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR PIPINGS
 AND FITTINGS REVIEWED AND APPROVED BY THE DESIGN
 PROFESSIONAL OF RECORD.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  