| 2015-08-04 08:15:24 | 1ST REVIEW: FBC 2010 MECHANICAL |
| | PERMIT #15060558 FERRIC CHLORIDE FACILITY |
| | 8/4/15 |
| | |
| | 1) SUBMIT MSDS SHEETS FOR THE FERRIC CHLORIDE |
| | 2) REFER TO SECTIONS 414.3 FBC-10 BUILDING AND 502.9 |
| | FBC-10 MECHANICAL, AND PROVIDE AN EXHAUST VENTILATION |
| | PLAN FOR THE STORAGE FACILITY. |
| | PROVIDE ON THE PLAN: A) VENTILATION CALCULATIONS B) THE |
| | SOURCE OF MAKEUP AIR. C) THE LOCATION OF THE EXHAUST |
| | FAN(S). D) FAN EQUIPMENT SCHEDULES E) SEQUENCE OF |
| | OPERATION DIAGRAM AND NARRATIVE DECRIPTION- REFER TO |
| | SECTION 502.8.1.1 FBC-10 MECHANICAL- SYSTEMS |
| | REQUIREMENTS: |
| | EXHAUST VENTILATION SYSTEMS SHALL COMPLY WITH ALL OF |
| | THE FOLLOWING: |
| | 1. THE INSTALLATION SHALL BE IN ACCORDANCE WITH THIS |
| | CODE. |
| | 2. MECHANICAL VENTILATION SHALL BE PROVIDED AT A RATE |
| | OF NOT LESS THAN 1 CFM PER SQUARE FOOT [0.00508 M3/(S ? |
| | M2)] OF FLOOR AREA OVER THE STORAGE AREA. |
| | 3. THE SYSTEMS SHALL OPERATE CONTINUOUSLY UNLESS |
| | ALTERNATE DESIGNS ARE APPROVED. |
| | 4. A MANUAL SHUTOFF CONTROL SHALL BE PROVIDED OUTSIDE |
| | OF THE ROOM IN A POSITION ADJACENT TO THE ACCESS DOOR |
| | TO THE ROOM OR IN ANOTHER APPROVED LOCATION. THE SWITCH |
| | SHALL BE A BREAK-GLASS OR OTHER APPROVED TYPE AND SHALL |
| | BE LABELED: VENTILATION SYSTEM EMERGENCY SHUTOFF. |
| | 5. THE EXHAUST VENTILATION SHALL BE DESIGNED TO |
| | CONSIDER THE DENSITY OF THE POTENTIAL FUMES OR VAPORS |
| | RELEASED. FOR FUMES OR VAPORS THAT ARE HEAVIER THAN |
| | AIR, EXHAUST SHALL BE TAKEN FROM A POINT WITHIN 12 |
| | INCHES (305 MM) OF THE FLOOR. FOR FUMES OR VAPORS THAT |
| | ARE LIGHTER THAN AIR, EXHAUST SHALL BE TAKEN FROM A |
| | POINT WITHIN 12 INCHES (305 MM) OF THE HIGHEST POINT OF |
| | THE ROOM. |
| | 6. THE LOCATION OF BOTH THE EXHAUST AND INLET AIR |
| | OPENINGS SHALL BE DESIGNED TO PROVIDE AIR MOVEMENT |
| | ACROSS ALL PORTIONS OF THE FLOOR OR ROOM TO PREVENT THE |
| | ACCUMULATION OF VAPORS. |
| | 7. THE EXHAUST AIR SHALL NOT BE RECIRCULATED TO |
| | OCCUPIED AREAS IF THE MATERIALS STORED ARE CAPABLE OF |
| | EMITTING HAZARDOUS VAPORS AND CONTAMINANTS HAVE NOT |
| | BEEN REMOVED. AIR CONTAMINATED WITH EXPLOSIVE OR |
| | FLAMMABLE VAPORS, FUMES OR DUSTS; FLAMMABLE, HIGHLY |
| | TOXIC OR TOXIC GASES; OR RADIOACTIVE MATERIALS SHALL |
| | NOT BE RECIRCULATED. |
| | 8) SHEET M-STD-03 (INCLUSIVE OF ALL PERMIT PLAN SETS |
| | CONTAINING THIS SHEET): REVISE NOTES #10 & 13 |
| | REFERENCING THE CITY OF TALLAHASSEE FIRE HYDRANT |
| | COMPLIANCE INFORMATION. |
| | 9) BASED ON THE SOILS REPORT- PIPE BEDDING AND |
| | DEWATERING GUIDELINES, PLEASE PROVIDE PIPE TRENCH |
| | CROSS-SECTION DETAILS FOR TYPICAL INSTALLATIONS AND |
| | HIGH WATER TABLE INSTALLATIONS. INDICATE TRENCH |
| | DIMENSIONS, PIPE EMBEDMENT DEPTHS, BEDDING MATERIALS |
| | AND THICKNESSES, COMPACTION AND BACKFILLING |
| | SPECIFICATIONS. |
| | 10) PROVIDE CIVIL DRAWINGS THAT INCLUDE OVERALL |
| | UNDERGROUND PIPING LAYOUTS, AND ENLARGED AREA DRAWINGS |
| | DEPICTING THE UNDERGROUND PIPINGS SPECIFICALLY |
| | SERVICING EACH TANK, FACILITY, BUILDING, ETC. |
| | 11) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR PIPINGS |
| | AND FITTINGS REVIEWED AND APPROVED BY THE DESIGN |
| | PROFESSIONAL OF RECORD. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |