Plan Review Notes
Plan Review Notes For Permit 15060558
Permit Number 15060558
Review Stop B
Sequence Number 1
Notes
Date Text
2015-07-27 08:24:21BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15060558 FERRIC CHLORIDE FACILITY
 ADD: 4395 EASLEY ST.
 CONT: TBD/ TO BE DETERMINED
 CONTACT: KURT PFEFFER, P. E.
 TEL: (561)997-8070
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: MON. JULY 27/ 2015
 ACTION: DENIED
  
 NOTE: SPECIFICATION BOOKS WILL NOT BE REVIEWED AS PART
 OF ANY PLAN REVIEW IF SUBMITTED THEY GET STAMPED VOID.
  
 1) PLEASE EITHER REMOVE THE INDEX SHEETS 0002-6-GEN.02
 THROUGH 0005-6-GEN.05 OR VOID THEM OUT THEY ARE OF NO
 USE TO THIS PROJECT THE WAY IT WAS SUBMITTED. THE PLANS
 DO NOT FOLLOW THE INDEX BEING BROUGHT IN BY BUILDING
 TYPES. 107.2.1.4 QUALITY OF BUILDING PLANS.
  
 2) SHEET 0241-S GEN-01 GENERAL STRUCTURAL NOTES, NOTE
 G-3 PLEASE NOTE CORRECT PALM BEACH COUNTY AMENDMENTS,
 THE CITY OF WEST PALM BEACH IS UNDER HOME RULE AND THE
 CITY HAS ITS OWN CHAPTER 1 AMENDMENTS. 2010 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION.
  
 3A) THIS PERMIT WILL REQUIRE A RESIDENT INSPECTOR.
 PLEASE REVIEW 2010 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, SECTION 2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER INSPECTIONS
 SERVICES. THE BUILDING OFFICIAL MAY MAKE, OR CAUSE TO
 BE MADE BY OTHERS, THE INSPECTIONS REQUIRED BY SECTION
 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS OF
 RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER
 INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR
 QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED
 FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT
 BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING
 AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE.
 THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY
 AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES:
  
 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 2. FOR ALL MAJOR STRUCTURAL ALTERATIONS
 3. WHERE THE CONCRETE DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F ?C) IN EXCESS OF 3000
 POUNDS PER SQUARE INCH
 4. FOR PILE DRIVING
 5. FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE
 FOOT
 6. FOR BUILDINGS MORE THAN 2 STORIES IN HEIGHT
 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR
 METHODS OF CONSTRUCTION
  
 3B) RESIDENT INSPECTOR FORMS MUST BE SIGNED BY ALL
 PARTIES NOTARIZED AND RETURNED TO THE BUILDING
 DEPARTMENT.
 FORMS E-MAILED TO: [email protected] THURS.
 JULY 02/2015 07:25 AM.
  
 3C) FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected] OR [email protected]
  
 3D) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE
 SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD:
 [email protected] OR [email protected]
  
 3E) INFORMATIONAL!!!! NOTE FOR PAPER PLANS 3 SETS OF
 DOCUMENTS ARE REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT
 ISSUANCE, THE PERMIT LIBRARIAN WILL E-MAIL YOU, THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE RESIDENT INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS.
  
 3F) INFORMATIONAL!!!!! PLEASE CALL THE CITY OF WEST
 PALM BEACHES AUTOMATED TELEPHONE INSPECTIONS LINE (561)
 805-6700) FOR IN-PROGRESS INSPECTIONS FOR AUDITING OF
 JOBSITE INSPECTIONS. NOTE IF INSPECTIONS ARE NOT CALLED
 IN, THE PERMIT EXPIRES 6 MONTHS AFTER THE PERMIT
 ISSUANCE DATE. A RENEWAL PERMIT WOULD BE REQUIRED AT
 THAT POINT.
  
 4) SHEET 0241-S GEN-01 GENERAL STRUCTURAL NOTES, HAS A
 HEADING FOR FOUNDATION WORK BUT THERE IS NO CRITERIA
 LISTED FOR THE SOILS INVESTIGATION REPORT, DATE AND
 COMPANY COMPLETING THE SOILS INVESTIGATION. 2010 FBC-B
 1803.5.2. FOUNDATION NOTE F-2 PROVIDES THE ALLOWABLE
 SOILS BEARING PRESSURES BUT THERE IS NO DOCUMENTATION
 OF A SOILS ANALYSIS AND EVALUATION EVER TAKING PLACE.
  
 5) PLEASE NOTE THAT A COPY OF DUNKELBERGER TESTING
 REPORT HD145002 APRIL 10, 2014 WAS SUBMITTED BY E-MAIL
 FOR REVIEW. THIS REPORT WILL NEED TO EITHER HAVE A HARD
 COPY SIGNED AND SEALED OR THE ELECTRONIC PEDDS
 SIGNATURE FOR ELECTRONIC VERSIONS OF THIS DOCUMENT.
  
 5A) DUNKELBERGER TESTING REPORT HD145002 APRIL 10,
 2014, PAGE 12 UNDER THE HEADING 9.2 VIBRO-COMPACTION
 VIBRO-COMPACTION FOR THE PROJECT SHOULD BE CARRIED OUT
 BY AN EXPERIENCED CONTRACTOR EMPLOYING A GROUND
 IMPROVEMENT PLAN THAT HE/SHE PREPARES. THE PLAN SHOULD
 UTILIZE CENTER-TO-CENTER SPACING FOR THE
 VIBRO-COMPACTION POINTS THAT ARE NORMALLY USED IN
 GRANULAR SOILS TO ACHIEVE 80 PERCENT RELATIVE DENSITY.
 BEFORE ADOPTION, THE GROUND IMPROVEMENT PLAN SHOULD BE
 REVIEWED BY THE GEOTECHNICAL ENGINEER AND STRUCTURAL
 ENGINEER FOR CONFORMANCE WITH THE INTENT OF THE
 FOUNDATION DESIGN.
 PLEASE PROVIDE FOR REVIEW BY THE BUILDING DEPARTMENT
 FOR COMPLIANCE.
  
 6) SHEET 0334-S-FER-01:
 6A) NOTE # 3 INDICATES THE PRE-ENGINEERED METAL
 BUILDING SHALL BE DESIGNED PER THE 2010 FBC-B AND LIVE
 LOADS SHOWN ON DRAWINGS S-GEN-01. PLEASE PROVIDE THE
 SHOP DRAWINGS FOR THIS STRUCTURE, TO BE REVIEWED BY THE
 ENGINEER OF RECORD AND STAMPED WITH THEIR SHOP DRAWING
 STAMP OF APPROVAL.
  
 6B) NOTE THIS BUILDING HAS A METAL ROOF PANEL SYSTEM
 ANCHORED TO PURLINS. PLEASE PROVIDE THE SPACING FOR THE
 PURLINS AND PRODUCT APPROVAL AS REQUIRED BY: FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS:
 (31) (D) ROOFING PRODUCTS AND ASSEMBLIES
  
 6C) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 6D) SHEET 0334-S-FER-01 NOTE # 3 INDICATES THE
 PRE-ENGINEERED METAL BUILDING SHALL BE DESIGNED PER THE
 2010 FBC-B WIND PROVISIONS PLEASE PROVIDE THE POSITIVE
 AND NEGATIVE PRESSURES FOR A OPEN BUILDING FOR ROOF
 ZONES 1, 2 & 3 FOR A BUILDING OF THIS HEIGHT.
 COMPONENTS & CLADDING PRESSURES POSITIVE & NEGATIVE
 TABLE 1609.2(2) .
  
 7) PLEASE PROVIDE THE MSDS SHEETS FOR FERRIC CHLORIDE
 TO SEE IF THIS CHEMICAL IS CONSIDERED A HAZARDOUS
 MATERIAL IN THE QANITIES TO BE STORED AT THIS SITE.
 PLEASE PROVIDE HOWL THIS CHEMICAL WILL BE STORED,
 LIQUID, UNDER PRESSURE, PER CENT OF CONCENTRATION. THIS
 CHEMICAL IS CONSIDERED A CORROSIVE, HOW WILL IT BE
 CONTAINED TO NOT EAT UP THE METAL SUPPORTS AND BUILDING
 ROOF? 2010 FBC-B (F) TABLE 414.2.5(1)(1) CORROSIVES.
  
 8) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  