Plan Review Notes
Plan Review Notes For Permit 15060557
Permit Number 15060557
Review Stop P
Sequence Number 1
Notes
Date Text
2015-07-23 14:33:161)SHT. 0202-M-OCS-02 SHOWS A 4" CDRN TO THE SANITARY
 SYSTEM. WILL THIS CONDENSATE BE OF A CORROSIVE NATURE?
 IF SO, THE WASTE SHALL DISCHARGE THROUGH A NEUTRALIZING
 DEVICE OR DILUTION TANK PER THE 2010 FPC SEC.803.2.
 2) SHT. 0204-M-OCS-04 - LIST THE SPECIFIC CIVIL SHEET
 FOR THE CONTINUATION OF THE 1 1/2" DRAIN FROM THE
 CONDENSATE PUMP.WPB AMEND. TO FBC SEC. 107.2.1.
 3) SUBMIT COMPLETE CIVIL DRAWINGS THAT SHOW ALL THE
 PIPING ASSOCIATED WITH THIS STRUCTURE/PROCESS.
 4) SHT.0766-M-STD-09 - DETAIL 1542102 -THIS COMMENT IS
 GENERIC FOR ALL PERMIT APPLICATIONS. THE WYE SHALL BE
 INSTALLED IN THE DIRECTION OF FLOW. 2010 FBC-PLUMBING
 SEC. 706.3.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  