| Plan Review Notes For Permit 15060557 |
| Permit Number |
15060557 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-07-23 14:33:16 | 1)SHT. 0202-M-OCS-02 SHOWS A 4" CDRN TO THE SANITARY | | | SYSTEM. WILL THIS CONDENSATE BE OF A CORROSIVE NATURE? | | | IF SO, THE WASTE SHALL DISCHARGE THROUGH A NEUTRALIZING | | | DEVICE OR DILUTION TANK PER THE 2010 FPC SEC.803.2. | | | 2) SHT. 0204-M-OCS-04 - LIST THE SPECIFIC CIVIL SHEET | | | FOR THE CONTINUATION OF THE 1 1/2" DRAIN FROM THE | | | CONDENSATE PUMP.WPB AMEND. TO FBC SEC. 107.2.1. | | | 3) SUBMIT COMPLETE CIVIL DRAWINGS THAT SHOW ALL THE | | | PIPING ASSOCIATED WITH THIS STRUCTURE/PROCESS. | | | 4) SHT.0766-M-STD-09 - DETAIL 1542102 -THIS COMMENT IS | | | GENERIC FOR ALL PERMIT APPLICATIONS. THE WYE SHALL BE | | | INSTALLED IN THE DIRECTION OF FLOW. 2010 FBC-PLUMBING | | | SEC. 706.3. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|