| Plan Review Notes For Permit 15060555 |
| Permit Number |
15060555 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-07-26 09:32:10 | 1) SUBMIT ALL DRAWINGS THAT ARE APPLICABLE FOR THIS | | | PORTION OF THE PROJECT. WPB AMEND. TO 2010 FBC SEC. | | | 107.2.1. | | | 2) THE INSTALLATION OF THE FUEL TANK SHALL COMPLY WITH | | | NFPA 30, SEC.4.2 THROUGH 4.6, & CHAPTER 5. | | | 3) INDICATE IF THE FUEL IS A COMBUSTIBLE OR FLAMMABLE | | | LIQUID AND INDICATE THE CLASS OF LIQUID PER NFPA 30, | | | SEC.1.7.3.1 & 1.7.3.2. | | | 4) SUBMIT THE MSDS FOR THE DIESEL FUEL.WPB AMEND. TO | | | 2010 FBC SEC. 107.2.1. | | | 5) INDICATE ON THE PLANS WHAT THE FUEL TANK IS | | | SUPPLYING..WPB AMEND. TO 2010 FBC SEC. 107.2.1. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|