| Date |
Text |
| 2015-08-05 07:21:47 | 1ST REVIEW: FBC 2010 MECHANICAL |
| | PERMIT #15060555 DIESEL FUEL TANK |
| | 8/5/15 |
| | |
| | 1) REFER TO SECTION 301.12 FBC-10 MECHANICAL: THE |
| | DIESEL FUEL TANK AND ALL OTHER ASSOCIATED EXTERIOR |
| | EQUIPMENT SHALL BE DESIGNED AND INSTALLED TO WITHSTAND |
| | 170 MPH WIND LOADS AS OUTLINED IN SECTION 1609 FBC-10 |
| | BUILDING. PLEASE PROVIDE THE WINDLOAD DESIGN CRITERIA |
| | ON THE PLAN AND INSTALLATIOMN DETAILS AND NOTES TO SHOW |
| | COMPLIANCE. |
| | 2) SUBMIT A MANUFACTURER'S DATA SHEET FOR THE TANK WITH |
| | A REVIEW AND APPROVAL SIGN-OFF STAMP BY THE ENGINEER OF |
| | RECORD. |
| | 3) SHEET M-STD-03 (INCLUSIVE OF ALL PERMIT PLAN SETS |
| | CONTAINING THIS SHEET): REVISE NOTES #10 & 13 |
| | REFERENCING THE CITY OF TALLAHASSEE FIRE HYDRANT |
| | COMPLIANCE INFORMATION. |
| | 4) BASED ON THE SOILS REPORT- PIPE BEDDING AND |
| | DEWATERING GUIDELINES, PLEASE PROVIDE PIPE TRENCH |
| | CROSS-SECTION DETAILS FOR TYPICAL INSTALLATIONS AND |
| | HIGH WATER TABLE INSTALLATIONS. INDICATE TRENCH |
| | DIMENSIONS, PIPE EMBEDMENT DEPTHS, BEDDING MATERIALS |
| | AND THICKNESSES, COMPACTION AND BACKFILLING |
| | SPECIFICATIONS. |
| | 5) PROVIDE CIVIL DRAWINGS THAT INCLUDE OVERALL |
| | UNDERGROUND PIPING LAYOUTS, AND ENLARGED AREA DRAWINGS |
| | DEPICTING THE UNDERGROUND PIPINGS SPECIFICALLY |
| | SERVICING EACH TANK, FACILITY, BUILDING, ETC. |
| | 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR PIPINGS AND |
| | FITTINGS REVIEWED AND APPROVED BY THE DESIGN |
| | PROFESSIONAL OF RECORD. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |