2015-08-05 07:21:471ST REVIEW: FBC 2010 MECHANICAL
 PERMIT #15060555 DIESEL FUEL TANK
 8/5/15
  
 1) REFER TO SECTION 301.12 FBC-10 MECHANICAL: THE
 DIESEL FUEL TANK AND ALL OTHER ASSOCIATED EXTERIOR
 EQUIPMENT SHALL BE DESIGNED AND INSTALLED TO WITHSTAND
 170 MPH WIND LOADS AS OUTLINED IN SECTION 1609 FBC-10
 BUILDING. PLEASE PROVIDE THE WINDLOAD DESIGN CRITERIA
 ON THE PLAN AND INSTALLATIOMN DETAILS AND NOTES TO SHOW
 COMPLIANCE.
 2) SUBMIT A MANUFACTURER'S DATA SHEET FOR THE TANK WITH
 A REVIEW AND APPROVAL SIGN-OFF STAMP BY THE ENGINEER OF
 RECORD.
 3) SHEET M-STD-03 (INCLUSIVE OF ALL PERMIT PLAN SETS
 CONTAINING THIS SHEET): REVISE NOTES #10 & 13
 REFERENCING THE CITY OF TALLAHASSEE FIRE HYDRANT
 COMPLIANCE INFORMATION.
 4) BASED ON THE SOILS REPORT- PIPE BEDDING AND
 DEWATERING GUIDELINES, PLEASE PROVIDE PIPE TRENCH
 CROSS-SECTION DETAILS FOR TYPICAL INSTALLATIONS AND
 HIGH WATER TABLE INSTALLATIONS. INDICATE TRENCH
 DIMENSIONS, PIPE EMBEDMENT DEPTHS, BEDDING MATERIALS
 AND THICKNESSES, COMPACTION AND BACKFILLING
 SPECIFICATIONS.
 5) PROVIDE CIVIL DRAWINGS THAT INCLUDE OVERALL
 UNDERGROUND PIPING LAYOUTS, AND ENLARGED AREA DRAWINGS
 DEPICTING THE UNDERGROUND PIPINGS SPECIFICALLY
 SERVICING EACH TANK, FACILITY, BUILDING, ETC.
 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR PIPINGS AND
 FITTINGS REVIEWED AND APPROVED BY THE DESIGN
 PROFESSIONAL OF RECORD.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER