| Date |
Text |
| 2016-03-25 12:41:32 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15060554 WASTE GAS BURNER |
| | ADD: 4395 EASLEY ST. |
| | CONT: TBD/ TO BE DETERMINED |
| | CONTACT: KURT PFEFFER, P. E. |
| | TEL: (561)997-8070 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 3RD REVIEW |
| | DATE: FRI. MARCH 25/ 2016 |
| | ACTION: BUILDING PROVISO |
| | |
| | 1) SHEET 0298 M-ADF-39 WHEN MEASURED SCALES ABOUT 12.4 |
| | FEET ABOVE THE FLANGE #150. PLEASE PROVIDE ADDITIONAL |
| | INFORMATION IF THE SCHEDULE 5S SST PIPE WILL REQUIRE |
| | LATERAL RESISTING SYSTEM FOR THE HEIGHT OF THE PIPE AS |
| | WELL FOR THE WIND DESIGN OF 180 MPH. |
| | |
| | LATERAL FORCE-RESISTING SYSTEM 2010 FBC-B 1604.4 |
| | ANALYSIS. LOAD EFFECTS ON STRUCTURAL MEMBERS AND THEIR |
| | CONNECTIONS SHALL BE DETERMINED BY METHODS OF |
| | STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT EQUILIBRIUM, |
| | GENERAL STABILITY, GEOMETRIC COMPATIBILITY AND BOTH |
| | SHORT- AND LONG-TERM MATERIAL PROPERTIES. EVERY |
| | STRUCTURE SHALL BE DESIGNED TO RESIST THE OVERTURNING |
| | EFFECTS CAUSED BY THE LATERAL FORCES SPECIFIED IN THIS |
| | CHAPTER. SEE SECTION 1609 FOR WIND LOADS? |
| | |
| | THE DESIGNER OF RECORD IN THE COMMENT RESPONSE DOES |
| | PROVIDE THE WIND DESIGN CRITERIA AND THE GAS BURNER |
| | MANUFACTURER WILL BE SUBMITTING CALCULATIONS WITH SHOP |
| | DRAWINGS DEMONSTRTING COMPLIANCE WITH THE REQUIRED 180 |
| | VULT WIND LOADS. |
| | |
| | BEFORE SHOP DRAWINGS ARE TO BE SUBMITTED THE ENGINEER |
| | OF RECORD FOR REVIEW AND APPROVAL BEFORE BEING |
| | SUBMITTED TO THE BUILDING DEPARTMENT. |
| | FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL |
| | FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE |
| | ENGINEER OF RECORD FOR REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |